| 2016-12-29 09:54:44 | 5TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #16041147 | | | 12/28/16 | | | | | | 1) THE REVISED AC CALCULATIONS BY KO ENERGY DESIGN | | | APPEAR TO BE FOR ONE SINGLE 2-BEDROOM RESIDENCE, AND | | | INCLUDE TOTAL COOLING AND HEATING LOADS, AND "DUCT | | | SIZING". THE PLANS BY BUCHANAN P.E. CONSULTING INC. ARE | | | SHOWING 5 "DUCTLESS" THROUGH THE WALL AC UNITS SERVING | | | ONLY THE LIVING ROOMS AND KITCHENS AND NO BEDROOMS OF 5 | | | DIFFERENT APARTMENTS. AS NOTED IN PREVIOUS REVIEWS, | | | THESE CONFLICTS NEED TO BE CORRECTED. PLEASE NOTE | | | MINIMUM HEATING IS REQUIRED FOR ALL OCCUPIED SPACES PER | | | SECTION 309.1. | | | | | | 2) PROVIDE AN AC EQUIPMENT SCHEDULE ON THE PLAN TO | | | MATCH THE SYSTEM DATA IN THE CALCULATIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|