| Plan Review Notes For Permit 16041147 |
| Permit Number |
16041147 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-20 11:03:45 | 2ND REVIEW MECHANICAL | | | PERMIT #16041147 | | | 7/20/16 | | | | | | 1) THE COMMENTS FROM THE 1ST REVIEW STILL EXIST. I HAVE | | | REPRINTED THEM BELOW. PLEASE NOTE THAT MINIMUM HEATING | | | IS REQUIRED FOR ALL OCCUPIABLE SPACES PER SECTION | | | 309.1. THE PLANS DO NOT INDICATE COMPLIANCE. | | | | | | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16041147 | | | 4/29/16 | | | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW AC SYSTEMS IN THE LIVING ROOMS- REFER TO SECTION | | | C403.2.1 FBC ENERGY CONSERVATION. | | | 2) PROVIDE EQUIPMENT SCHEDULES ON THE PLANS FOR THE NEW | | | AC SYSTEMS, INSTALLATION DETAILS, AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|