| | ELECTRICAL PLAN REVIEW COMMENTS |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - SHOW LOCATION OF EXISTING SUB PANEL "A" ON THE FLOOR |
| | PLAN TO VERIFY WORK CLEARANCES, LOAD CALCULATIONS AND |
| | PANEL SCHEDULE REFLECT A RANGE BUT HOWEVER ON THE |
| | KITCHEN LAYOUT THERE IS A COOKTOP AND AN OVEN ? MODIFY |
| | ACCORDINGLY. FBC 107 MINIMUM PLAN REVIEW CRITERIA. |
| | - KITCHEN ISLAND RECEPTACLE OUTLETS ON BOTH ENDS SHALL |
| | BE GFCI PROTECTED AND INSTALLED NO MORE THAN 12'' BELOW |
| | THE COUNTERTOP. FBC R SECTIONS E3902.6 & E3901.4.2 |
| | - A/C DISCONNECT SEEMS TO BE BEHIND THE COMPRESSOR, |
| | PLEASE REFLECT PROPER WORK CLEARANCE. OUTSIDE GFCI |
| | RECEPTACLE SHALL ?WR? IN ADDITION OF BEING INSTALLED IN |
| | A ?WP? ENCLOSURE. FBC R SECTIONS E4002.9 & E3405.1 |
| | - NFPA SECTION 29.8.3.4(6). SMOKE ALARMS AND SMOKE |
| | DETECTORS SHALL NOT BE INSTALLED WITHIN A 36 IN. (910 |
| | MM) HORIZONTAL PATH FROM A DOOR TO A BATHROOM |
| | CONTAINING A SHOWER OR TUB UNLESS LISTED FOR |
| | INSTALLATION IN CLOSE PROXIMITY TO SUCH LOCATIONS. |
| | RELOCATE THE UNITS ACCORDINGLY. |
| | - ONE AND TWO FAMILY DWELLINGS SHALL HAVE OUTDOOR |
| | RECEPTACLES IN BOTH BACK & FRONT OF THE HOUSE. FBC R |
| | E3901.7 |
| | - FBC-E R404.1 A MINIMUM OF 75 PERCENT OF THE LAMPS IN |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL BE |
| | HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF THE |
| | PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL CONTAIN |
| | ONLY HIGH EFFICACY LAMPS. |
| | - PROVIDE AN ATTIC ENTRANCE LIGHT THAT IS SWITCHED AS |
| | REQUIRED AND ILLUMINATION SHALL BE SUFFICIENT FOR |
| | SERVICING THE AIR HANDLING UNIT. FBC R SECTION E3903.4 |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER'S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE |
| | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| | APPRECIATED. |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |