| 2016-04-28 19:35:54 | JOB PERMIT NUMBER: 16041147 |
| | JOB ADDRESS: 914 3RD ST 1 |
| | WEST PALM BEACH FLORIDA |
| | DATE: APRIL 28 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - ELECTRICAL SERVICE RISER SHOWS 2? CONDUIT WITH 2 SETS |
| | OF 3/0 AWG IN PARALLEL , HOWEVER TABLE ANNEX C CONDUIT |
| | FILL STATES ONLY 5 WIRES FIT ASSUMING EITHER IMC OR RMC |
| | IS BEING INSTALLED. CLARIFY AND CORRECT ACCORDINGLY ? |
| | - PROVIDE INTERSYSTEM BONDING TERMINAL STRIP ON THE |
| | GROUNDING DETAIL IN THE RISER DIAGRAM. NEC 250.94 |
| | - ELECTRICAL NOTE OF LIGHTING NEEDING TO BE 50 % HIGH |
| | EFFICIENT IS INCORRECT FBC-E R 404.1 A MINIMUM 75 % |
| | LAMPS SHALL BE HIGH EFFICACY , FURTHER MORE CHANGE THE |
| | CODE REFERENCE OF NEC 2008 TO THE APPLICABLE 2011 IN |
| | TAMPER RESISTANT RECEPTACLE NOTE. |
| | - SERVICE EQUIPMENT TO INCLUDE ALL PERMANENT PLAQUES OF |
| | NEC 225.37 , INTERIOR PANELBOARDS TO HAVE |
| | IDENTIFICATION OF SOURCE OF SUPPLY IN ACCORDANCE WITH |
| | NEC 408.4 (B) |
| | - FOR FINAL INSPECTION ARC-FLASH HAZARD WARNING LABELS |
| | AND AVAILABLE FAULT CURRENT MARKINGS MUST BE ON |
| | ELECTRICAL APPARATUS SUITABLE TO WITHSTAND ENVIRONMENT. |
| | - ALL ELECTRICAL BOXES IN A DEMISING WALL SHALL COMPLY |
| | WITH NEC 300.21 AND FBC SECTION 714. ANY FIRE RATED |
| | STRUCTURE THAT IS COMPROMISED SHALL BE RETURNED TO ITS |
| | ORIGINAL FIRE-RATING WITH APPROVED FIRE SEALING |
| | MATERIAL. |
| | - PROVIDE SPECS ON A/C WALL UNITS TO VERIFY IF THEY |
| | PROVIDE HEAT PER FBC-R 303.9 EVERY DWELLING UNIT |
| | HABITABLE ROOM SHALL BE CAPABLE OF MAINTAINING 68 |
| | DEGREES FAHRENHEIT AT 3 FT ABOVE FLOOR AND 2 FT FROM |
| | EXTERIOR WALLS. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6713 |
| | [email protected] |
| | |