| Date |
Text |
| 2016-04-27 19:07:34 | PLAN REVIEW COMMENTS |
| | |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | ELECTRICAL |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THERE ARE NO APPROVED ELECTRICAL PLANS FOR THIS |
| | PROJECT AND NO ELECTRICAL PERMIT HAS BEEN ISSUED. |
| | THEREFORE, THIS CAN NOT BE AN ELECTRICAL REVISION. A |
| | SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED. |
| | FBC 105.1 NOTE: THIS REVISION AND FEES CAN BE APPLIED |
| | TO THE ELECTRICAL PERMIT APPLICATION. |
| | |
| | 2) SUBMIT TWO SETS OF ELECTRICAL PLANS WITH THE PRINTED |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. FBC 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED |
| | AND DRAWN UPON SUITABLE MATERIAL. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. |
| | |
| | 3) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS. |
| | |
| | 4) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE. |
| | |
| | 5) FBC- 107.3.5.3 - PROVIDE SMOKE ALARMS PURSUANT TO |
| | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. SMOKE |
| | ALARMS ARE ALSO REQUIRED ON EACH ADDITIONAL STORY OF |
| | THE DWELLING. |
| | R314.3 LOCATION. |
| | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | 1. IN EACH SLEEPING ROOM. |
| | 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS. |
| | 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| | BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL |
| | SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| | DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| | INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| | ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| | THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| | IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| | WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE |
| | INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM |
| | DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT |
| | THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE |
| | ALARMS IN THE INDIVIDUAL UNIT. |
| | |
| | 6) RECEPTACLES ON COVERED PORCH AND SECOND FLOOR DECK |
| | SHALL BE LISTED FOR WET LOCATIONS AND GFCI PROTECTED. |
| | FBCR-E3905.11 AND |
| | FBCR-E3902.3 |
| | |
| | 7) THE OUTLET BOXES SHALL LISTED AND MARKED BY THE |
| | MANUFACTURER FOR THE CEILING FAN THAT THEY WILL |
| | SUPPORT. FBCR-E3905.8 |
| | |
| | |