2016-05-04 15:07:17 
 1ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. PROVIDE SITE PLAN WITH LOCATION OF RAMP.
  
 2. RAMP SLOPE NOT TO EXCEED 1:20.
  
 402.2 COMPONENTS.
 ACCESSIBLE ROUTES SHALL CONSIST OF ONE OR MORE OF THE
 FOLLOWING COMPONENTS: WALKING SURFACES WITH A RUNNING
 SLOPE NOT STEEPER THAN 1:20, DOORWAYS, RAMPS, CURB
 RAMPS EXCLUDING THE FLARED SIDES, ELEVATORS, AND
 PLATFORM LIFTS. ALL COMPONENTS OF AN ACCESSIBLE ROUTE
 SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF
 CHAPTER 4 AND 208.3.1.
  
 2. HANDRAILS.
 RAMPS WITH A RISE GREATER THAN 6 INCHES (152 MM) SHALL
 HAVE HANDRAILS ON BOTH SIDES. HANDRAILS SHALL COMPLY
 WITH SECTION 1012.
  
 1012
 HANDRAILS FOR STAIRWAYS AND RAMPS SHALL BE ADEQUATE IN
 STRENGTH AND ATTACHMENT IN ACCORDANCE WITH SECTION
 1607.8. HANDRAILS REQUIRED FOR STAIRWAYS BY SECTION
 1009.15 SHALL COMPLY WITH SECTIONS 1012.2 THROUGH
 1012.9. HANDRAILS REQUIRED FOR RAMPS BY SECTION 1010.9
 SHALL COMPLY WITH SECTIONS 1012.2 THROUGH 1012.8.
  