| Plan Review Notes For Permit 16041133 |
| Permit Number |
16041133 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-27 17:18:37 | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | | PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED. | | | | | | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | | | 107.2.1 | | | (1) PROVIDE OWNER/AGENT SIGNATURE AND DATE ON ALL | | | FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING | | | CONSTRUCTION FORM. | | | (2) PROVIDE ACCURATE WORK DESCRIPTION OF WORK TO BE | | | DONE ON PERMIT APPLICATION. EXAMPLE INSTALLATION OF TWO | | | A/C SYSTEMS WITH DUCTWORK. INSTALLATION OF TWO | | | MINI-SPLIT SYSTEMS. | | | (3) PROVIDE FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING | | | CONSTRUCTION FORM FOR UNIT 414. | | | (4) MODEL NUMBERS ON THE EQUIPMENT SCHEDULE ARE BOTH | | | CONDENSING UNITS. PROVIDE AHU WHICH MATCHES AS PER AHRI | | | ON EQUIPMENT SCHEDULE. | | | (5) UNIT #402 ON THE ENERGY CALCULATIONS SHOW 24000 BTU | | | OF COOLING. PROVIDE EQUIPMENT TO MEET THIS LOAD. | | | | | | 109.3 BUILDING PERMIT VALUATIONS | | | VALUE ON PERMIT APPLICATION IS TO LOW. RECALCULATE JOB | | | OR PROVIDE COPY OF PROPOSAL. | | | |
|