Plan Review Notes
Plan Review Notes For Permit 16041117
Permit Number 16041117
Review Stop M
Sequence Number 5
Notes
Date Text
2016-12-29 08:14:105TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16041117
 12/28/16
  
 THE FOLLOWING REVIEW IS BASED ON THE REVISED PLANS FROM
 MESSLER AND ASSOCIATES DATED 12/14/16
  
 1) CORRECT SCOPE OF WORK #8 ON THE COVER SHEET THAT
 INDICATES NO CHANGE TO THE AC SYSTEM TO MATCH THE SCOPE
 OF WORK SHOWN.
  
 2) THE REVISED PLAN IS NOW INDICATING TWO 5-TON RTU'S A
 SHARING A RETURN AIR PLENUM WHICH REQUIRES A SMOKE
 DETECTOR PER SECTION 606.2.2.
  
 3) THE EQUIPMENT SCHEDULE FOR THE NEW 5-TON SYSTEM IS
 INCOMPLETE- PROVIDED THE MANUFACTURER, THE AHRI
 CERTIFICATION NUMBER, AND THE ELECTRICAL DATA.
  
 4) PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW TOILET
 ROOM EXHAUST FAN, AND SHOW THE EXHAUST DUCT TERMINATION
 LOCATION.
  
 5) THE COMBUSTION AIR CALCULATION INDICATES A SHORTAGE
 OF 9937 CU. FT. OF INDOOR SPACE. PLEASE CLARIFY HOW THE
 SHORTAGE WILL BE COMPENSATED FOR. IF THE AIR IS TO BE
 SUPPLIED MECHANICALLY REFER TO SECTION 304.9 FUEL GAS
 AND PROVIDE A CALCULATION.
  
 6) THE AC CALCULATIONS INDICATE A HEATING LOAD OF 39864
 BTUH. THE AC SCHEDULE INDICATES A SHORTAGRE OF 17664
 BTUH.
  
 7) PLEASE REMOVE THE AC LAYOUT PLANS FROM THE AC
 CALCULATIONS UNLESS THEY ARE TO BE USED ON THE
 PROJECT.\
  
 8) REFER TO SECTION 301.15 AND PROVIDE SITE SPECIFIC
 WIND LOAD ENGINEERING FOR INSTALLATION OF THE NEW RTU
 IN COMPLIANCE WITH SECTION 1609 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  