2017-01-04 07:02:36BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041117
 ADD: 6611 S. DIXIE HWY.
 CONT: T. B. D./ TO BE DETERMINED
 TEL: 856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 5TH REVIEW
 DATE: WED. JAN. 04/2017
 ACTION: DENIED
  
 1) THE COVERSHEET UNDER THE HEADING SCOPE OF WORK
 STATEMENT # 8 AIR CONDITIONING EXISTING NO CHANGES.
 THERE IS A DISCREPANCY IN PLANS, SHEET 2 OF 3 THE ROOF
 PLAN INDICATES TO INSTALL A SECOND 5 TON ROOF TOP UNIT,
 MAINTAIN 36 INCHES APART. 2014 FLORIDA BUILDING CODE W
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED, A DISCREPANCY IN PLANS.
  
 2) SHEET 2 OF 3 INDICATING A NEW 5 TON ROOF TOP UNIT,
 PLEASE PROVIDE THE TYPE OF ROOF SHEATHING/ DECK
 MATERIAL TO BE PENETRATED, PLEASE PROVIDE THE TYPE OF
 ROOF FRAMING, IF HEADERS ARE REQUIRED, IF A SECONDARY
 ROOF JOIST IS REQUIRED( DOUBLER) AND OR IF BAR JOIST
 SYSTEM AND TYPE & SIZE OF ANGLE IRON TO BE USED FOR
 FRAMING, IF JOIST STIFFNER IS REQUIRED?
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3) SHEET 2 OF 3 INDICATES A NEW ROOF TOP A/C UNIT,
 PLEASE PROVIDE PRODUCT INFORMATION FOR THE NEW ROOF TOP
 CURB, ANCHORAGE OF CURB TO ROOF DECK, AND THE
 CONNECTION OF THE
 ROOF TOP UNIT TO CURB. FOR ALL ROOF TOP EQUIPMENT,
 CURBS OR A/C STANDS, DETAILED ATTACHMENT TO THE ROOF
 FRAMING & DECK AS WELL AS FROM THE CURB OR ROOF STAND
 TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 4) SHEET 2 OF 3 INDICATES A NEW ROOF TOP A/C UNIT, THE
 PLANS DO NOT INDICATE THE ELEVATION OF THE ROOF ABOVE
 GRADE NOR IF THERE IS A PARAPET REQUIREDTO TRANSVERSE
 BEFORE GAINING ACCESS TO THE ROOF TOP UNIT. 2014 FBC-B
 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES. WHERE EQUIPMENT AND APPLIANCES REQUIRING
 ACCESS ARE INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT
 A HEIGHT EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL
 BE PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS,
 THE EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL
 TO THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE.
 SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) HIGH OR
 WALKING ON ROOFS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  