| 2016-12-15 10:40:31 | 4TH REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS |
| | |
| | 1.HAS NOT COMPLIED RISER STILL SHOWS HORIZONTAL DRY |
| | VENTS 3. THE HORIZONTAL DRY VENT AT THE END OF THE |
| | RISER DIAGRAM IS NOT ALLOWED AND IS NOT REQUIRED TO |
| | VENT SYSTEM PLEASE REMOVE. PER FBC PL 905.3 VENT |
| | CONNECTION TO DRAINAGE SYSTEM. |
| | EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| | PIPE. |
| | 905.4 VERTICAL RISE OF VENT. |
| | EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT |
| | LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM |
| | OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. |
| | |
| | 2.NOT COMPLIED SHOW WC CONNECTING TO HORIZONTAL DRAIN |
| | DOES NOT NEED TO BE INDIVIDUALLY VENTED 5. IF THE |
| | TOILET IS A FLOOR MOUNT IT SHOULD CONNECT TO THE |
| | HORIZONTAL RUN OF DRAIN PLEASE CLARIFY. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | |
| | 3.PARTIALLY COMPLIED DISHWASHER SHALL DRAIN INTO A |
| | INDIRECT WASTE RECEPTOR NOT A AIR GAP FITTING 6. THE |
| | THREE COMPARTMENT SINK AND THE DISH WASHER SHALL BE |
| | INDIRECTLY WASTED. PER FBC PL 802.1.7 COMMERCIAL |
| | DISHWASHING MACHINES. |
| | THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE |
| | SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A |
| | STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION |
| | 802.2. |
| | 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS. |
| | SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF |
| | UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN |
| | THE PREPARATION, SERVING OR EATING OF FOOD SHALL |
| | DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK |
| | TO THE DRAINAGE SYSTEM. |
| | |
| | |