Plan Review Notes
Plan Review Notes For Permit 16041117
Permit Number 16041117
Review Stop G
Sequence Number 4
Notes
Date Text
2017-01-13 13:58:193RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS
  
 PARTIALLY COMPLIED 1. PLEASE SHOW REQUIRED PRESSURE
 REGULATORS AND THE ANSUL SYSTEM EMERGENCY SHUT OFF
 VALVE. PER WPB AMEND TO FBC 107.2.1
  
  
 NOT COMPLIED PLEASE PROVIDE 6. THE MANUFACTURE SPEC
 SHEETS SHALL LIST THE SPECIFIC STANDARD THEY MEET SUCH
 AS NFPA 54, NFPA 58 ALSO FBC FUEL GAS 623.1 COOKING
 APPLIANCES.
 COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT
 INSTALLATION, INCLUDING RANGES, OVENS, STOVES,
 BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND
 BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI
 Z21.1, ANSI Z21.58 OR ANSI Z83.11 AND SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
  
  
  
 NEW COMMENT:
  
 1.THE COMBUSTION AIR CALCULATION INDICATES A SHORTAGE
 OF 9937 CU. FT. OF INDOOR SPACE. PLEASE CLARIFY HOW THE
 SHORTAGE WILL BE COMPENSATED FOR. IF THE AIR IS TO BE
 SUPPLIED MECHANICALLY REFER TO SECTION 304.9 FUEL GAS
 AND PROVIDE A CALCULATION..
  
 2. INDICATE ON THE PLAN THE SYSTEM PRESSURE. PER FBC
 GAS 402.2
  
 3. PROVIDE THE TABLES USED TO SIZE THE SYSTEM. WPB
 AMEND TO FBC 107.2.1
  
 IN ORDER TO TO GET THIS PLAN APPROVED I SUGGEST THAT WE
 MEET TO GO OVER MY COMMENTS ON THE PLAN PLEASE CONTACT
 ME TO SET A DATE.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  