| 2017-01-13 13:58:19 | 3RD REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: PREVIOUS |
| | |
| | PARTIALLY COMPLIED 1. PLEASE SHOW REQUIRED PRESSURE |
| | REGULATORS AND THE ANSUL SYSTEM EMERGENCY SHUT OFF |
| | VALVE. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | NOT COMPLIED PLEASE PROVIDE 6. THE MANUFACTURE SPEC |
| | SHEETS SHALL LIST THE SPECIFIC STANDARD THEY MEET SUCH |
| | AS NFPA 54, NFPA 58 ALSO FBC FUEL GAS 623.1 COOKING |
| | APPLIANCES. |
| | COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT |
| | INSTALLATION, INCLUDING RANGES, OVENS, STOVES, |
| | BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND |
| | BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI |
| | Z21.1, ANSI Z21.58 OR ANSI Z83.11 AND SHALL BE |
| | INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | |
| | |
| | NEW COMMENT: |
| | |
| | 1.THE COMBUSTION AIR CALCULATION INDICATES A SHORTAGE |
| | OF 9937 CU. FT. OF INDOOR SPACE. PLEASE CLARIFY HOW THE |
| | SHORTAGE WILL BE COMPENSATED FOR. IF THE AIR IS TO BE |
| | SUPPLIED MECHANICALLY REFER TO SECTION 304.9 FUEL GAS |
| | AND PROVIDE A CALCULATION.. |
| | |
| | 2. INDICATE ON THE PLAN THE SYSTEM PRESSURE. PER FBC |
| | GAS 402.2 |
| | |
| | 3. PROVIDE THE TABLES USED TO SIZE THE SYSTEM. WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | IN ORDER TO TO GET THIS PLAN APPROVED I SUGGEST THAT WE |
| | MEET TO GO OVER MY COMMENTS ON THE PLAN PLEASE CONTACT |
| | ME TO SET A DATE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |