| 2016-11-08 08:49:35 | 3RD REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHOW TOILET DISPENSER 7"-9" OFF THE FRONT EDGE OF |
| | TOILET. PER FBC ACC 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL |
| | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES |
| | NOT ALLOW CONTINUOUS PAPER FLOW. |
| | |
| | 2. SHOW THE WATER CLOSET 16" MIN AND 18" MAX OFF THE |
| | SIDE WALL TO CENTERLINE OF TOILET. PER FBC ACC 604.2 |
| | LOCATION. |
| | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION |
| | |
| | 3. THE HORIZONTAL DRY VENT AT THE END OF THE RISER |
| | DIAGRAM IS NOT ALLOWED AND IS NOT REQUIRED TO VENT |
| | SYSTEM PLEASE REMOVE. PER FBC PL 905.3 VENT CONNECTION |
| | TO DRAINAGE SYSTEM. |
| | EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| | PIPE. |
| | 905.4 VERTICAL RISE OF VENT. |
| | EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT |
| | LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM |
| | OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. |
| | |
| | 4.THE NOTE ON THE RISER ABOVE THE TOILET READS 11/2" IS |
| | THIS INDICATING PIPE SIZE WATER CLOSET SHALL BE ON MIN |
| | OF 3" PIPE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. IF THE TOILET IS A FLOOR MOUNT IT SHOULD CONNECT TO |
| | THE HORIZONTAL RUN OF DRAIN PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 6. THE THREE COMPARTMENT SINK AND THE DISH WASHER SHALL |
| | BE INDIRECTLY WASTED. PER FBC PL 802.1.7 COMMERCIAL |
| | DISHWASHING MACHINES. |
| | THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE |
| | SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A |
| | STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION |
| | 802.2. |
| | 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS. |
| | SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF |
| | UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN |
| | THE PREPARATION, SERVING OR EATING OF FOOD SHALL |
| | DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK |
| | TO THE DRAINAGE SYSTEM. |
| | |
| | |