2016-11-08 09:23:493RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16041117
 11/1/16
  
 1) THE AC PLANS AND SUBMITTALS ARE IN CONFLICT:
  
 A) SHEET 2 SHOWS A GROUND-MOUNTED 10 TON CONDENSER,
 SHEET 3 SHOWS A 5-RON ROOF MOUNTED CONDENSER.
 B) THE RESPONSE NARRATIVE INDICATES A REPLACED 5-TON
 SYSTEM AND A NEW 5-TON SYSTEM TO BE INSTALLED.
 CONSISTENTLY LABEL AND IDENTIFY THE LOCATIONS OF THE
 TWO SYSTEMS ON SHEETS 2 & 3.
 C) NEITHER SHEET 2 OR 3 PROVIDE COMPLETE DUCT LAYOUT
 PLANS. SHEET 2 DOES NOT SHOW ANY AIR DISTRIBUTION IN
 THE JUICE BAR AREA OR DINING ROOM. AN AIR DISTRIBUTION
 PLAN FROM ENERGY HOUSE TECHNOLOGY HAS BEEN SUBMITTED
 ALONG WITH CALCULATIONS THAT DO NOT MATCH WITH SHEET 2.
 D) THE SUBMITTED AC LOAD SUMMARY CALCULATIONS MUST BE
 SIGNED AND SEALED BY AN ENGINEER PER SECTION C403.2.1
 EXCEPTION FBC-14 ENERGY CONSERVATION.
 E) THE 10" DUCTS SUPPLYING 500 CFMS OF AIR ON SHEET 2
 ARE UNDERSIZED AT 0.1 FRICTION RATE.
  
 2) AS PREVIOUSLY REQUESTED PROVIDE AC EQUIPMENT
 SCHEDULES ON THE PLAN.
  
 3) AS PREVIOUSLY PROVIDE AIR BALANCE CALCULATIONS.
  
 4) AS PREVIOUSLY REQUESTED PROVIDE A ROOF PLAN SHOWING
 ALL REQUIRED CLEARANCE DISTANCE MEASUREMENTS FOR AIR
 INTAKES TO EXHAUST OUTLETS, AND FROM EQUIPMENT TO ROOF
 EDGES.
  
 5) MANUFACTURER'S SPECIFICATIONS FOR A GAS-FIRED
 CHARBROILER AND VERTICAL BROILER HAVE BEEN SUBMITTED,
 HOWEVER NEITHER APPLIANCE IS SHOWN ON THE PLAN. PLEASE
 REMOVE THE SUBMITTALS OR SHOW THE LOCATIONS OF THE
 APPLIANCES ON NTHE PLAN.
  