Plan Review Notes
Plan Review Notes For Permit 16041117
Permit Number 16041117
Review Stop G
Sequence Number 3
Notes
Date Text
2016-12-15 10:39:493RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS
  
 PARTIALLY COMPLIED 1. PLEASE SHOW REQUIRED SHUT OFF
 VALVES DRIP LEGS AND PRESSURE REGULATORS AND THE ANSUL
 SYSTEM EMERGENCY SHUT OFF VALVE. PER WPB AMEND TO FBC
 107.2.1
 SHOW PRESSURE REGULATORS PLAN IS INDICATING 2PSI SYSTEM
 BUT IT IS SIZED TO A .5PSI SYSTEM PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 NOT COMPLIED PLEASE PROVIDE 6. THE MANUFACTURE SPEC
 SHEETS SHALL LIST THE SPECIFIC STANDARD THEY MEET SUCH
 AS NFPA 54, NFPA 58 ALSO FBC FUEL GAS 623.1 COOKING
 APPLIANCES.
 COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT
 INSTALLATION, INCLUDING RANGES, OVENS, STOVES,
 BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND
 BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI
 Z21.1, ANSI Z21.58 OR ANSI Z83.11 AND SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
  
 NEW COMMENT:
  
 1. THE COMBUSTION AIR CALCULATIONS ARE NOT ACCURATE THE
 TOTAL BTU LISTED IN CALCULATION IS 156,000 THE TOTAL
 BTU LISTED ON GAS RISER IS 437,140 . BY MY CALCULATIONS
 21'857 CU FT OF AIR IS REQUIRED. PLEASE CLARIFY PER
 FBC-2014 FUEL GAS CODE SEC. 304.