| Notes |
| Date |
Text |
| 2016-11-08 09:55:32 | 2ND REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE SHOW REQUIRED SHUT OFF VALVES DRIP LEGS AND | | | PRESSURE REGULATORS AND THE ANSUL SYSTEM EMERGENCY SHUT | | | OFF VALVE. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. PLEASE INDICATE THE MODELS ON MANUFACTURE SPEC | | | SHEET. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. THE BTU LOADS ON THE RISER DO NOT MATCH BTU LOAD ON | | | MANUFACTURE SPECS PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 4. MANUFACTURE SPECS SHOW 3/4 GAS SUPPLY'S THE RISER | | | SHOWS 1/2 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 5., THE VERTICAL BROILER YOU PROVIDED MANUFACTURE SPECS | | | FOR IS NOT SHOWN ON THE FLOOR PLAN OR RISER DIAGRAM | | | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 6. THE MANUFACTURE SPEC SHEETS SHALL LIST THE SPECIFIC | | | STANDARD THEY MEET SUCH AS NFPA 54, NFPA 58 ALSO FBC | | | FUEL GAS 623.1 COOKING APPLIANCES. | | | COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT | | | INSTALLATION, INCLUDING RANGES, OVENS, STOVES, | | | BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND | | | BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI | | | Z21.1, ANSI Z21.58 OR ANSI Z83.11 AND SHALL BE | | | INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S | | | INSTALLATION INSTRUCTIONS. |
|