Plan Review Notes
Plan Review Notes For Permit 16041117
Permit Number 16041117
Review Stop B
Sequence Number 2
Notes
Date Text
2016-08-04 06:56:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041117
 ADD: 6611 S. DIXIE HWY.
 CONT: T. B. D./ TO BE DETERMINED
 TEL: 856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. AUGUST 04/ 2016
 ACTION: DENIED
  
 1) COVERSHEET:
 1A) COMPLIED.
 1B) 2ND REQUEST. THE DESIGNER OF RECORD HAS INDICATED
 THIS IS A LEVEL 1 ALTERATION. PLEASE REVIEW 2014
 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL
 NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
 1ST ROUND COMMENT. THE DESIGNER OF RECORD HAS NOT
 INDICATED COMPLIANCE WITH 2014 FBC-EXISTING BUILDING
 CODE 301.1 GENERAL. THE REPAIR, ALTERATION, CHANGE OF
 OCCUPANCY, ADDITION OR RELOCATION OF ALL EXISTING
 BUILDINGS SHALL COMPLY WITH ONE OF THE METHODS LISTED
 IN SECTIONS 301.1.1 THROUGH 301.1.3 AS SELECTED BY THE
 APPLICANT. APPLICATION OF A METHOD SHALL BE THE SOLE
 BASIS FOR ASSESSING THE COMPLIANCE OF WORK PERFORMED
 UNDER A SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE
 CODE OFFICIAL. SECTIONS 301.1.1 THROUGH 301.1.3 SHALL
 NOT BE APPLIED IN COMBINATION WITH EACH OTHER.
  
 2) 2ND REQUEST. SHEET 2 OF 3 SHOWS NEW WALLS WITHIN THE
 ACCESSIBLE REST ROOM. 2014 EXISTING BUILDING CODE LEVEL
 II 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 2014 FBC-ACCESS. CODE 604.3.1 SIZE. CLEARANCE AROUND A
 WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES
 (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.
  
 3) 2ND REQUEST. SHEET 2 OF 3 SHOWS THE BACK AND SIDE
 GRAB BARS SHOW 33-36 INCHES CENTER LINE OF THE GRAB
 BAR. PLEASE SHOW COMPLIANCE WITH
 ACCESS. CODE 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 (840 MM) MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE,
  
 4)2ND REQUEST. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART,? DO NOT RECITE CODE SECTIONS!!!
 SHEET 2 OF 3 ON THE FLOOR PLAN INDICATES A NEW PASS
 THROUGH WINDOW BUT NO ELEVATIONS. PLEASE PROVIDE
 COMPLIANCE WITH: 2014 FBC-ACCESS. CODE :
 904.5 FOOD SERVICE LINES. COUNTERS IN FOOD SERVICE
 LINES SHALL COMPLY WITH 904.5. 904.5.1 SELF-SERVICE
 SHELVES AND DISPENSING DEVICES. SELF-SERVICE SHELVES
 AND DISPENSING DEVICES FOR TABLEWARE, DISHWARE,
 CONDIMENTS, FOOD AND BEVERAGES SHALL COMPLY WITH 308.
  
 904.5.2 TRAY SLIDES. THE TOPS OF TRAY SLIDES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) 2ND REQUEST. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART,? DO NOT RECITE CODE SECTIONS!!!
 SHEET 2 OF 3. PLEASE SHOW COMPLIANCE WITH; 2014
 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) 2ND REQUEST. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART,? DO NOT RECITE CODE SECTIONS!!!
 SHEET 2 OF 3. PLEASE SHOW COMPLIANCE WITH; 2014
 FBC-ACCESS. CODE 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES. PLEASE NOTE IF THE
 DINING COUNTER AT THE FRONT WINDOW IS A HIGH-TOP OR
 NOT. IF HIGH TOP ACCESSIBLE SEATING MUST BE THERE AS
 WELL.
  
 7) NOTATION ONLY!!! ADDITIONAL PERMITS ARE REQUIRED,
 FOR GAS APPLIANCES, AND THE HOOD, ANSEL SYSTEMS AND
 EXHAUST SYSTEMS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW
 COMMENTS FROM ALL DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  