Plan Review Notes
Plan Review Notes For Permit 16041117
Permit Number 16041117
Review Stop M
Sequence Number 1
Notes
Date Text
2016-05-05 10:45:151ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16041117
 5/5/16
  
 1) A NEW EXHAUST HOOD IS BEING INSTALLED IN THE
 KITCHEN: PLEASE PROVIDE MINIMUM VENTILATION AND AIR
 BALANCE CALCULATIONS FOR THE RESTAURANT- SEE TABLE
 403.3 FOR REQUIRED OUTDOOR AIR AND EXHAUST CFM'S AND
 RATES.
 2) THE WPB DEVELOPMENT SERVICES DEPARTMENT/BUILDING
 DIVISION REQUIRES SEPARATE PERMITS FOR KITCHEN HOOD
 EXHAUST AND FIRE SUPPRESSION SYSTEMS- PLEASE PLACE A
 NOTE ON THE PLAN ACCORDINGLY.
 3) THE PLAN IS ALSO INDICATING A NEW DISHWASHER WHICH
 REQUIRES A TYPE II EXHAUST HOOD AS NOTED IN SECTION
 507.2.2.. PLEASE PLACE A NOTE INDICATING PLANS TO BE
 SUBMITTED UNDER A SEPARATE PERMIT.
 4) NEW HEAT-PRODUCING APPLIANCES ARE SHOWN IN THE
 KITCHEN WHICH WILL CONTRIBUTE TO THE TOTAL HEAT LOAD OF
 THE SPACE- PLEASE PROVIDE AC COOLING AND HEATING
 CALCULATIONS AND VERIFY THAT THE EXISTING AC SYSTEMS
 CAN HANDLE THE INCREASED LOAD, OR PROVIDE PLANS AND
 SPECIFICATIONS FOR ANY NEW UPGRADES.
 5) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW GAS
 APPLIANCES AND INDICATE HOW THE AIR IS BEING PROVIDED-
 SEE SECTION 304 FBC-14 FUEL GAS.
 6) ALTHOUGH THE HOODS, FANS AND EXHAUST OUTLETS WILL BE
 UNDER SEPARATE PERMIT, PLEASE INDICATE WHERE THE
 EXHAUST OUTLETS WILL TERMINATE AND SHOW THE REQUIRED
 CLEARANCE DISTANCE MEASUREMENTS AS INDICATED IN
 SECTIONS 501.3.1 (2), 506.3.13.2, & 506.4.2.
  