2016-05-02 11:06:07JOB PERMIT NUMBER: 16041117
 JOB ADDRESS: 6611 S DIXIE HIGHWAY
 WEST PALM BEACH FLORIDA
 DATE: MAY 2 2016
  ELECTRICAL PLAN REVIEW COMMENTS
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - MEP SHEET , ALL 125-VOLT, SINGLEPHASE,15- AND
 20-AMPERE RECEPTACLES IN COMMERCIAL KITCHEN REQUIRE NEC
 210.8 GROUND FAULT CIRCUIT-INTERRUPTER PROTECTION(B)
 OTHER THAN DWELLING UNITS.
 - FBC-B 1006.2. EMERGENCY LIGHTING IS REQUIRED , INSIDE
 THE KITCHEN PREP AREA AND DINING ROOM AREA, EMERGENCY
 LIGHTING SHALL BE FED BY LIGHTING CIRCUIT OF SAME LOCAL
 AREA. *IF 3 OR MORE LIGHTING CIRCUITS SUPPLY THE AREA,
 EM LIGHTS MAY BE ON OWN CIRCUIT NEC 700.12 (F) (4).
 - C405.2.2.2 OCCUPANCY SENSORS. OCCUPANCY SENSORS SHALL
 BE INSTALLED IN ALL CLASSROOMS, CONFERENCE/MEETING
 ROOMS, EMPLOYEE LUNCH AND BREAK ROOMS, PRIVATE OFFICES,
 RESTROOMS, STORAGE ROOMS AND JANITORIAL CLOSETS, AND
 OTHER SPACES 300 SQUARE FEET (28 M2) OR LESS ENCLOSED
 BY FLOOR-TO-CEILING HEIGHT PARTITIONS. THESE AUTOMATIC
 CONTROL DEVICES SHALL BE INSTALLED TO AUTOMATICALLY
 TURN OFF LIGHTS WITHIN 30 MINUTES OF ALL OCCUPANTS
 LEAVING THE SPACE, AND SHALL EITHER BE MANUAL ON OR
 SHALL BE CONTROLLED TO AUTOMATICALLY TURN THE LIGHTING
 ON TO NOT MORE THAN 50 PERCENT POWER.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  