| 2016-05-02 11:06:07 | JOB PERMIT NUMBER: 16041117 |
| | JOB ADDRESS: 6611 S DIXIE HIGHWAY |
| | WEST PALM BEACH FLORIDA |
| | DATE: MAY 2 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - MEP SHEET , ALL 125-VOLT, SINGLEPHASE,15- AND |
| | 20-AMPERE RECEPTACLES IN COMMERCIAL KITCHEN REQUIRE NEC |
| | 210.8 GROUND FAULT CIRCUIT-INTERRUPTER PROTECTION(B) |
| | OTHER THAN DWELLING UNITS. |
| | - FBC-B 1006.2. EMERGENCY LIGHTING IS REQUIRED , INSIDE |
| | THE KITCHEN PREP AREA AND DINING ROOM AREA, EMERGENCY |
| | LIGHTING SHALL BE FED BY LIGHTING CIRCUIT OF SAME LOCAL |
| | AREA. *IF 3 OR MORE LIGHTING CIRCUITS SUPPLY THE AREA, |
| | EM LIGHTS MAY BE ON OWN CIRCUIT NEC 700.12 (F) (4). |
| | - C405.2.2.2 OCCUPANCY SENSORS. OCCUPANCY SENSORS SHALL |
| | BE INSTALLED IN ALL CLASSROOMS, CONFERENCE/MEETING |
| | ROOMS, EMPLOYEE LUNCH AND BREAK ROOMS, PRIVATE OFFICES, |
| | RESTROOMS, STORAGE ROOMS AND JANITORIAL CLOSETS, AND |
| | OTHER SPACES 300 SQUARE FEET (28 M2) OR LESS ENCLOSED |
| | BY FLOOR-TO-CEILING HEIGHT PARTITIONS. THESE AUTOMATIC |
| | CONTROL DEVICES SHALL BE INSTALLED TO AUTOMATICALLY |
| | TURN OFF LIGHTS WITHIN 30 MINUTES OF ALL OCCUPANTS |
| | LEAVING THE SPACE, AND SHALL EITHER BE MANUAL ON OR |
| | SHALL BE CONTROLLED TO AUTOMATICALLY TURN THE LIGHTING |
| | ON TO NOT MORE THAN 50 PERCENT POWER. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |