Plan Review Notes
Plan Review Notes For Permit 16041117
Permit Number 16041117
Review Stop B
Sequence Number 1
Notes
Date Text
2016-05-05 07:57:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041117
 ADD: 6611 S. DIXIE HWY.
 CONT: T. B. D./ TO BE DETERMINED
 TEL: 856-6655
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MAY 05/ 2016
 ACTION: DENIED
  
 1) COVERSHEET:
 1A) THE DESIGNER OF RECORD HAS NOT INDICATED TO WHAT
 CODE THESE PLANS WERE DESIGNED? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1B) THE DESIGNER OF RECORD HAS NOT INDICATED COMPLIANCE
 WITH 2014 FBC-EXISITNG BUILDING CODE 301.1 GENERAL. THE
 REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR
 RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY WITH
 ONE OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH
 301.1.3 AS SELECTED BY THE APPLICANT. APPLICATION OF A
 METHOD SHALL BE THE SOLE BASIS FOR ASSESSING THE
 COMPLIANCE OF WORK PERFORMED UNDER A SINGLE PERMIT
 UNLESS OTHERWISE APPROVED BY THE CODE OFFICIAL.
 SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED
 IN COMBINATION WITH EACH OTHER.
  
 2) SHEET 2 OF 3 SHOWS NEW WALLS WITHIN THE ACCESSIBLE
 REST ROOM. 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 2014 FBC-ACCESS. CODE 604.3.1 SIZE. CLEARANCE AROUND A
 WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES
 (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL.
  
 3) SHEET 2 OF 3 SHOWS THE BACK AND SIDE GRAB BARS SHOW
 33-36 INCHES CENTER LINE OF THE GRAB BAR. PLEASE SHOW
 COMPLIANCE WITH
 ACCESS. CODE 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 (840 MM) MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE,
  
 4) SHEET 2 OF 3 ON THE FLOOR PLAN INDICATES A NEW PASS
 THROUGH WINDOW BUT NO ELEVATIONS. PLEASE PROVIDE
 COMPLIANCE WITH: 2014 FBC-ACCESS. CODE :
 904.5 FOOD SERVICE LINES.
 COUNTERS IN FOOD SERVICE LINES SHALL COMPLY WITH 904.5.
  
 904.5.1 SELF-SERVICE SHELVES AND DISPENSING DEVICES.
 SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR
 TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES
 SHALL COMPLY WITH 308.
  
 904.5.2 TRAY SLIDES.
 THE TOPS OF TRAY SLIDES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 5) SHEET 2 OF 3. PLEASE SHOW COMPLIANCE WITH; 2014
 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) SHEET 2 OF 3. PLEASE SHOW COMPLIANCE WITH; 2014
 FBC-ACCESS. CODE 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES. PLEASE NOTE IF THE
 DINING COUNTER AT THE FRONT WINDOW IS A HIGH-TOP OR
 NOT. IF HIGH TOP ACCESSIBLE SEATING MUST BE THERE AS
 WELL.
  
 7) NOTATION ONLY!!! ADDITIONAL PERMITS ARE REQUIRED,
 FOR GAS APPLIANCES, AND THE HOOD AND EXHAUST SYSTEMS.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW
 COMMENTS FROM ALL DISCIPLINES:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  