| 2016-05-05 07:57:31 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16041117 |
| | ADD: 6611 S. DIXIE HWY. |
| | CONT: T. B. D./ TO BE DETERMINED |
| | TEL: 856-6655 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. MAY 05/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) COVERSHEET: |
| | 1A) THE DESIGNER OF RECORD HAS NOT INDICATED TO WHAT |
| | CODE THESE PLANS WERE DESIGNED? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 1B) THE DESIGNER OF RECORD HAS NOT INDICATED COMPLIANCE |
| | WITH 2014 FBC-EXISITNG BUILDING CODE 301.1 GENERAL. THE |
| | REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR |
| | RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY WITH |
| | ONE OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH |
| | 301.1.3 AS SELECTED BY THE APPLICANT. APPLICATION OF A |
| | METHOD SHALL BE THE SOLE BASIS FOR ASSESSING THE |
| | COMPLIANCE OF WORK PERFORMED UNDER A SINGLE PERMIT |
| | UNLESS OTHERWISE APPROVED BY THE CODE OFFICIAL. |
| | SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE APPLIED |
| | IN COMBINATION WITH EACH OTHER. |
| | |
| | 2) SHEET 2 OF 3 SHOWS NEW WALLS WITHIN THE ACCESSIBLE |
| | REST ROOM. 2014 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | 2014 FBC-ACCESS. CODE 604.3.1 SIZE. CLEARANCE AROUND A |
| | WATER CLOSET SHALL BE 60 INCHES (1525 MM) MINIMUM |
| | MEASURED PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES |
| | (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM THE REAR |
| | WALL. |
| | |
| | 3) SHEET 2 OF 3 SHOWS THE BACK AND SIDE GRAB BARS SHOW |
| | 33-36 INCHES CENTER LINE OF THE GRAB BAR. PLEASE SHOW |
| | COMPLIANCE WITH |
| | ACCESS. CODE 609.4 POSITION OF GRAB BARS. GRAB BARS |
| | SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES |
| | (840 MM) MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE |
| | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE, |
| | |
| | 4) SHEET 2 OF 3 ON THE FLOOR PLAN INDICATES A NEW PASS |
| | THROUGH WINDOW BUT NO ELEVATIONS. PLEASE PROVIDE |
| | COMPLIANCE WITH: 2014 FBC-ACCESS. CODE : |
| | 904.5 FOOD SERVICE LINES. |
| | COUNTERS IN FOOD SERVICE LINES SHALL COMPLY WITH 904.5. |
| | |
| | 904.5.1 SELF-SERVICE SHELVES AND DISPENSING DEVICES. |
| | SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR |
| | TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES |
| | SHALL COMPLY WITH 308. |
| | |
| | 904.5.2 TRAY SLIDES. |
| | THE TOPS OF TRAY SLIDES SHALL BE 28 INCHES (710 MM) |
| | MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | |
| | 5) SHEET 2 OF 3. PLEASE SHOW COMPLIANCE WITH; 2014 |
| | FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF DINING |
| | SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 6) SHEET 2 OF 3. PLEASE SHOW COMPLIANCE WITH; 2014 |
| | FBC-ACCESS. CODE 226.2 DISPERSION. DINING SURFACES AND |
| | WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE |
| | DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING |
| | DINING SURFACES AND WORK SURFACES. PLEASE NOTE IF THE |
| | DINING COUNTER AT THE FRONT WINDOW IS A HIGH-TOP OR |
| | NOT. IF HIGH TOP ACCESSIBLE SEATING MUST BE THERE AS |
| | WELL. |
| | |
| | 7) NOTATION ONLY!!! ADDITIONAL PERMITS ARE REQUIRED, |
| | FOR GAS APPLIANCES, AND THE HOOD AND EXHAUST SYSTEMS. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | THE REVIEWS FOR THIS PROJECT ARE COMPLETE. TO VIEW |
| | COMMENTS FROM ALL DISCIPLINES: |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT |
| | US.ASPX. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |