| 2016-06-03 15:41:30 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16041113 | | | 6/3/16 | | | | | | 1) ENERGY GAUGE TOTAL PERFORMANCE COMPLIANCE | | | CALCULATIONS HAVE BEEN SUBMITTED: A) THE PROJECT IS | | | INCORRECTLY CLASSIFIED AS A "NEW FINISHED BUILDING" ON | | | PAGE 2. B) THE DOCUMENT HAS NOT BEEN SIGNED AND DATED | | | BY THE OWNER AGENT, ARCHITECT, ELECTRICAL DESIGNER, AND | | | LIGHTING DESIGNER- SEE PAGE 3. REFER TO SECTIONS C401.4 | | | AND C103.1.1.1.2 FBC-14 ENERGY CONSERVATION. | | | | | | 2) AC COOLING AND HEATING CALCULATIONS HAVE BEEN | | | SUBMITTED WITHOUT SIGNATURES AND DATES. | | | | | | 3) IT APPEARS FROM THE CALCULATIONS THAT NEW | | | REPLACEMENT HEAT PUMPS ARE TO BE PROVIDED. PLEASE NOTE | | | THAT ON THE PLAN AND PROVIDED EQUIPMENT SCHEDULES. | | | | | | 4) SHEET M-1: THE VENTILATION CALCULATIONS DO NOT | | | APPEAR TO BE COMPLIANT WITH TABLE 403.3 OR ASHRAE 62.1- | | | 2010 EACH OF WHICH REQUIRES O/A CFM RATES PER PERSON AS | | | WELL AS CFMS PER SQUARE FOOT | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|