| Notes |
| Date |
Text |
| 2016-05-06 17:10:23 | | | | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | | | | GAS COMMENTS: SEPARATE PERMIT REQUIRED | | | | | | 1. SUBMIT AN EXISTING ISOMETRIC DRAWING THAT CLEARLY | | | SHOWS PIPE SIZE AND LONGEST DISTANCE FROM METER PER | | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | | | | | | 2. BTU LOAD OF EXISTING AND NEW APPLIANCES AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE FBC-2014 | | | FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) | | | THRU 402.4(37). | | | | | | | | | 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR NEW | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | | | | 4. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | | PSI. |
|