| Date |
Text |
| 2016-05-04 11:23:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHET A 0.00 AND ALL OTHER APPLICABLE SHEETS, THERE |
| | IS NO REFERNCE TO THE REVIEW AND/OR COMPLIANCE WITH THE |
| | APPLICABLE FIRE CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITIONS OF NFPA 1 AND NFPA 101 INCLUDING, BUT |
| | NOT LIMITED TO, NFPA 101, CHAPTER 29 EXISTING HOTELS |
| | AND DORMITORIES AND ALL OTHER APPLICABLE CODES OR |
| | STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | 2) THERE IS NO REFERENCE TO IF THE BUILDING WILL BE |
| | OCCUPIED DURING THE CONSTRUCTION PERIOD. WILL THE WORK |
| | BE DONE IN PHASES, SEPARATE FLOORS? WILL SOME OF THE |
| | FLOOORS NEED TO BE INSPECTED, FINALED AND OCCUPIED |
| | BEFORE OTHER FLOORS ARE STARTED? |
| | |
| | PLEASE PROVIDE INFORMATION AND INDICATIONS. |
| | |
| | 3) IF THE BUILDING WILL BE OCCUPIED, A LIFE SAFETY PLAN |
| | SHALL BE PROVIDED TO ENSURE PROPER EGRESS. |
| | |
| | PLEASE PROVIDE A LIFE SAFETY PLAN. IF PHASED, PLEASE |
| | PROVIDE THE APPLICABLE PHASED LIFE SAFETY PLANS. |
| | |
| | 4) PLEASE PROVIDE INDICATION THAT ALL LIFE SAFETY |
| | SYSTEMS; FIRE ALARM, FIRE SPRINKLER, FIRE PUMP AND |
| | INCLUDING THE EMRGENCY GENERATOR, IF EXISTING, ETC, AND |
| | ALL EQUIPMENT SHALL REMAIN ACTIVE DURING ALL |
| | CONSTRUCTION. |
| | |
| | 5) PROVIDE INDICATIONS THAT THE FIRE ALARM AND FIRE |
| | SPRINKLER WORK SHALL BE COMPLETED BY CERTIFIED LIFE |
| | SAFETY CONTRACTORS UNDER SEPARATE SHOP DRAWINGS. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |