2016-05-05 10:29:401ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16041065
 5/5/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING
 CODE, ALTERED EXISTING SYSTEMS:
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.
 PLEASE PROVIDE MINIMUM VENTILATION CALCULATIONS ON THE
 PLAN PER TABLE 403.3 FBC-14 MECHANICAL.
 2) SOME OF THE VAV BOXES SHOWN HAVE TO BE RELOCATED
 FROM ABOVE THE LIGHTING FIXTURES TO ALLOW FOR CLEAR
 ACCESS FOR MAINTENANCE AND REPLACEMENT- SEE SECTION
 306.9 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER