2016-09-28 11:12:55MECHANICAL PROVISO
 PERMIT #16041056
 9/28/16
  
 THE CURRENT MECHANICAL PLANS ARE APPROVED WITH A
 CONTINGENCY FOR A REVISION TO BE SUBMITTED TO CORRECT A
 DEFICIENCY IN THE SMOKING LOUNGE EXHAUST VENTILATION
 SYSTEM.
 AS PREVIOUSLY NOTED IN PRIOR REVIEWS, RECIRCULATION OF
 AIR IN THE LOUNGE AREA IS PROHIBITED PER TABLE 403.3
 FOOTNOTE B, AND SECTION 403.2.1 ITEM 3. ALL AIR
 SUPPLIED TO SUCH AREAS SHALL BE EXHAUSTED, HOWEVER THE
 PLAN INDICATES ONLY 2700 CFMS OF THE 3000 CFMS SUPPLED
 ARE BEING EXHAUSTED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER