| 2016-09-28 11:12:55 | MECHANICAL PROVISO | | | PERMIT #16041056 | | | 9/28/16 | | | | | | THE CURRENT MECHANICAL PLANS ARE APPROVED WITH A | | | CONTINGENCY FOR A REVISION TO BE SUBMITTED TO CORRECT A | | | DEFICIENCY IN THE SMOKING LOUNGE EXHAUST VENTILATION | | | SYSTEM. | | | AS PREVIOUSLY NOTED IN PRIOR REVIEWS, RECIRCULATION OF | | | AIR IN THE LOUNGE AREA IS PROHIBITED PER TABLE 403.3 | | | FOOTNOTE B, AND SECTION 403.2.1 ITEM 3. ALL AIR | | | SUPPLIED TO SUCH AREAS SHALL BE EXHAUSTED, HOWEVER THE | | | PLAN INDICATES ONLY 2700 CFMS OF THE 3000 CFMS SUPPLED | | | ARE BEING EXHAUSTED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|