2016-08-24 16:22:351ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16041056
 8/24/16
  
 1) ENERGY FORM C402 MAY BE USED FOR ALTERATIONS,
 RENOVATIONS, AND BUILDING SYSTEMS, HOWEVER THE PROJECT
 IS A CHANGE OF OCCUPANCY- SEE SECTION C101.5.1.1 FBC-14
 ENERGY CONSERVATION.
  
 2) REFER TO TABLE 403.3 FOOTNOTE B, AND SECTION
 403.2.1(3)- RECIRCULATION OF AIR IN THE SMOKING LOUNGE
 IS PROHIBITED. THE CALCULATIONS INDICATE COMPLIANCE,
 HOWEVER ERV'S WILL TYPICALLY LEAK A SMALL PERCENTAGE OF
 RETURN AIR BACK INTO THE SUPPLY AIRSTREAM WHICH IS
 LIMITED TO 10% PER SECTION 514.4. PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS INDICATING THE LEAKAGE
 RATE OF THE ERV.
  