| Plan Review Notes For Permit 16041056 |
| Permit Number |
16041056 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-08-24 16:22:35 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16041056 | | | 8/24/16 | | | | | | 1) ENERGY FORM C402 MAY BE USED FOR ALTERATIONS, | | | RENOVATIONS, AND BUILDING SYSTEMS, HOWEVER THE PROJECT | | | IS A CHANGE OF OCCUPANCY- SEE SECTION C101.5.1.1 FBC-14 | | | ENERGY CONSERVATION. | | | | | | 2) REFER TO TABLE 403.3 FOOTNOTE B, AND SECTION | | | 403.2.1(3)- RECIRCULATION OF AIR IN THE SMOKING LOUNGE | | | IS PROHIBITED. THE CALCULATIONS INDICATE COMPLIANCE, | | | HOWEVER ERV'S WILL TYPICALLY LEAK A SMALL PERCENTAGE OF | | | RETURN AIR BACK INTO THE SUPPLY AIRSTREAM WHICH IS | | | LIMITED TO 10% PER SECTION 514.4. PLEASE SUBMIT | | | MANUFACTURER'S SPECIFICATIONS INDICATING THE LEAKAGE | | | RATE OF THE ERV. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|