| 2016-08-29 13:08:46 | 3RD ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | PENDING COMMENTS: | | | | | | 1. PLEASE CLARIFY SHEET 13-E SUBMITTED REFLECTING PANEL | | | SCHEDULES AND SERVICE ONE-LINE, IS THIS INSERT | | | INCORRECT OR IS IT PART OF CONSTRUCTION DOCUMENTS. ONE | | | SET HAS IT INCLUDED THE OTHER SET DOESNT. CLARIFY SHEET | | | IS NOT SIGNED AND SEALED BY EOR. FBC 107.3.5 | | | 2. PRIOR COMMENTS ADDRESSED. | | | 3. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|