2016-07-18 09:44:282ND REVIEW MECHANICAL
 PERMIT #16041056
 7/18/16
  
 1) THE RESUBMITTED PLANS INDICATE A CHANGE OF OCCUPANCY
 TO A2- PLEASE SUBMIT ENERGY CALCULATIONS PER SECTION
 C101.4.4 AND C401.2 FBC-14 ENERGY CONSERVATION.
  
 2) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, SUBMIT AC
 COOLING AND HEATING CALCULATIONS PER SECTION 403.2.1
 FBC-14 ENERGY CONSERVATION.
  
 3) M-1: THE VENTILATION CALCULATION FOR THE LOUNGE AREA
 BASED ON 45 PERSONS IS INCORRECT. THE OCCUPANT DENSITY
 PER TABLE 403.3 IS BASED ON 70 PERSONS PER SQ. FT.
 REFER TO SHEET 18-F- THE INTERIOR LOUNGE IS LISTED AT
 944 SQ. FT. WHICH RESULTS IN A 66 PERSON OCCUPANT
 DENSITY PER TABLE 403.3- PLEASE CORRECT.
  
 4) M-1: THE VENTILATION CALCULATION DOES NOT INCLUDE
 THE HUMIDOR ROOM, THE CORRIDOR/HALL 03, AND THE STORAGE
 ROOMS 1 & 2, . PLEASE NOTE THE HUMIDOR ROOM HAS A
 LISTED OCCUPANT LOAD OF 50 ON THE LIFE SAFETY PLAN-
 SHEET 18-F. A) CLARIFY WAT TYPE OF PRODUCTS, OR
 MATERIALS ARE BEING STORED IN THE STORAGE ROOMS.
  
 5) M-1: REFER TO TABLE 403.3 FOOTNOTE E AND INDICATE
 HOW EF-1 AND EF-2 WILL OPERATE- INTERMITTENTLY OR
 CONTINUOUSLY.
  
 6) AS PREVIOUSLY REQUESTED PROVIDE A COMPLETE
 CONDENSATE DISPOSAL PLAN THAT INCLUDES THE NEW 100 %
 O/A UNIT.
  
 7) PROVIDE A MECHANICAL ROOF PLAN SHOWING ALL REQUIRED
 CLEARANCES FOR THE OUTDOOR AIR INTAKES TO EXHAUST AND
 VENT OUTLETS- SEE SECTION 401.4.
  
 8) 2ND REQUEST FOR AN AIR DEVICE SCHEDULE.
  
 9) M-2 PROVIDE THE WIND LOAD DESIGN CRITERIA INCLUDING
 THE WIND SPEED, IMPORTANCE FACTOR, EXPOSURE CATEGORY,
 AND HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT- SECTION
 301.15.
  