| 2016-07-18 09:44:28 | 2ND REVIEW MECHANICAL |
| | PERMIT #16041056 |
| | 7/18/16 |
| | |
| | 1) THE RESUBMITTED PLANS INDICATE A CHANGE OF OCCUPANCY |
| | TO A2- PLEASE SUBMIT ENERGY CALCULATIONS PER SECTION |
| | C101.4.4 AND C401.2 FBC-14 ENERGY CONSERVATION. |
| | |
| | 2) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, SUBMIT AC |
| | COOLING AND HEATING CALCULATIONS PER SECTION 403.2.1 |
| | FBC-14 ENERGY CONSERVATION. |
| | |
| | 3) M-1: THE VENTILATION CALCULATION FOR THE LOUNGE AREA |
| | BASED ON 45 PERSONS IS INCORRECT. THE OCCUPANT DENSITY |
| | PER TABLE 403.3 IS BASED ON 70 PERSONS PER SQ. FT. |
| | REFER TO SHEET 18-F- THE INTERIOR LOUNGE IS LISTED AT |
| | 944 SQ. FT. WHICH RESULTS IN A 66 PERSON OCCUPANT |
| | DENSITY PER TABLE 403.3- PLEASE CORRECT. |
| | |
| | 4) M-1: THE VENTILATION CALCULATION DOES NOT INCLUDE |
| | THE HUMIDOR ROOM, THE CORRIDOR/HALL 03, AND THE STORAGE |
| | ROOMS 1 & 2, . PLEASE NOTE THE HUMIDOR ROOM HAS A |
| | LISTED OCCUPANT LOAD OF 50 ON THE LIFE SAFETY PLAN- |
| | SHEET 18-F. A) CLARIFY WAT TYPE OF PRODUCTS, OR |
| | MATERIALS ARE BEING STORED IN THE STORAGE ROOMS. |
| | |
| | 5) M-1: REFER TO TABLE 403.3 FOOTNOTE E AND INDICATE |
| | HOW EF-1 AND EF-2 WILL OPERATE- INTERMITTENTLY OR |
| | CONTINUOUSLY. |
| | |
| | 6) AS PREVIOUSLY REQUESTED PROVIDE A COMPLETE |
| | CONDENSATE DISPOSAL PLAN THAT INCLUDES THE NEW 100 % |
| | O/A UNIT. |
| | |
| | 7) PROVIDE A MECHANICAL ROOF PLAN SHOWING ALL REQUIRED |
| | CLEARANCES FOR THE OUTDOOR AIR INTAKES TO EXHAUST AND |
| | VENT OUTLETS- SEE SECTION 401.4. |
| | |
| | 8) 2ND REQUEST FOR AN AIR DEVICE SCHEDULE. |
| | |
| | 9) M-2 PROVIDE THE WIND LOAD DESIGN CRITERIA INCLUDING |
| | THE WIND SPEED, IMPORTANCE FACTOR, EXPOSURE CATEGORY, |
| | AND HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT- SECTION |
| | 301.15. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |