Plan Review Notes
Plan Review Notes For Permit 16041056
Permit Number 16041056
Review Stop B
Sequence Number 2
Notes
Date Text
2016-05-17 13:34:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041056
 ADD: 701 VILLAGE BLVD. SUITES: 201-202
 CONT: GREAT PATRIOT CONSTRUCTION
 TEL: 561-241-4765
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 17/2016
 ACTION: DENIED
  
 1) COVERSHEET/ 01-A:
  
 1A) UPPER RIGHT HAND CORNER OF THE PLANS UNDER THE
 HEADING OF NOTES THE BUILDING CLASSIFICATION IS
 INDICATES AS ASSEMBLY AND THE 2ND LINE THE OCCUPANCY
 PER THE FBC CHAPTER 6 ASSEMBLY (NON-SEPARATED).
 PLEASE NOTE THE DESIGNER OF RECORD HAS NOT DECLARED
 WHAT CLASSIFICATION TYPE OF OCCUPANCY, THIS APPEARS TO
 BE AN OCCUPANCY TYPE A2, SEE 2014 FBC-B 303.3.
  
 THE OTHER ISSUE DECLARING ASSEMBLY NON-SEPARATED PER
 CHAPTER 6 WOULD BE THE WRONG CODE SECTION FOR
 NON-SEPARATED USE. THE OTHER OCCUPANCY HAS NOT BEEN
 DECLARED.
  
 SEE 2014 FBC-B 508.3.1 OCCUPANCY CLASSIFICATION.
 NONSEPARATED OCCUPANCIES SHALL BE INDIVIDUALLY
 CLASSIFIED IN ACCORDANCE WITH SECTION 302.1. THE
 REQUIREMENTS OF THIS CODE SHALL APPLY TO EACH PORTION
 OF THE BUILDING BASED ON THE OCCUPANCY CLASSIFICATION
 OF THAT SPACE. IN ADDITION, THE MOST RESTRICTIVE
 PROVISIONS OF CHAPTER 9 WHICH APPLY TO THE NONSEPARATED
 OCCUPANCIES SHALL APPLY TO THE TOTAL NONSEPARATED
 OCCUPANCY AREA.
  
 1B) UNDER BOTH HEADINGS OF NOTES AND LOAD SCHEDULES,
 WIND DESIGN THE PLANS WERE DESIGNED TO A WIND EXPOSURE
 OF ?B?. TO BOTH THE WEST AND EAST THERE ARE VECTORS
 THAT MEET THE QUALIFICATIONS FOR A SURFACE ROUGHNESS
 C.FBC-B 1609.4.2. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30 FEET
 (9144 MM). THIS CATEGORY INCLUDES FLAT OPEN COUNTRY,
 AND GRASSLANDS. THIS SURFACE ROUGHNESS SHALL ALSO APPLY
 TO ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS B TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET (30 M)
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE
 ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN
 600 FEET (182.9 M) IN THE UPWIND DIRECTION AND A WIDTH
 GREATER THAN 150 FEET (46 M). PLEASE UPDATE THE WIND
 EXPOSURE TO AN C EXPOSURE AS WELL AS UPDATE THE
 PRESSURES FOR ALL BUILDING WIND ZONES 1-5, ALL ARE LOW,
 PLEASE ALSO REVIEW TABLE 1609.7(2) ADJUSTMENT FACTOR
 FOR BUILDING HEIGHT AND EXPOSURE .
  
 1C) UNDER THE HEADING OF LOAD SCHEDULE / WIND THE
 BUILDING RISK CATEGORY WAS HAND WRITTEN IN PLEASE
 PROVIDE THE CORRECT RISK FACTOR FOR THIS BUILDING.
 TABLE 1604.5.
  
 1D) UNDER THE HEADING NOTES, THE 2014 FBC-B WAS THE
 DOCUMENT THE PLANS WERE TO BE DESIGNED TO, PLEASE BE
 AWARE THE 2014 EXISTING BUILDING CODE IS THE OTHER CODE
 THIS REVIEW WILL OCCUR UNDER. THE DESIGNER OF RECORD
 HAS NOT INDICATED TO WHAT METHOD CODE COMPLIANCE WAS
 CONSIDERED. 2014 EXISTING BUILDING CODE 301.1 GENERAL.
 THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION
 OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY
 WITH ONE OF THE METHODS LISTED IN SECTIONS 301.1.1
 THROUGH 301.1.3 AS SELECTED BY THE APPLICANT.
 APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR
 ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A
 SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE
 OFFICIAL. SECTIONS 301.1.1 THROUGH 301.1.3 SHALL NOT BE
 APPLIED IN COMBINATION WITH EACH OTHER. WHERE THIS CODE
 REQUIRES CONSIDERATION OF THE SEISMIC FORCE-RESISTING
 SYSTEM OF AN EXISTING BUILDING SUBJECT TO REPAIR,
 ALTERATION, CHANGE OF OCCUPANCY, ADDITION OR RELOCATION
 OF EXISTING BUILDINGS, THE SEISMIC EVALUATION AND
 DESIGN SHALL BE BASED ON SECTION 301.1.4 REGARDLESS OF
 WHICH COMPLIANCE METHOD IS USED.
  
 1E) THE SITE AND BUILDING DATA LIST 3,427 SQ. FT. IN
 THIS BAY. SHEET 02-A LIST 17,724 SQ. FT. IN THE
 BUILDING, PLEASE PROVIDE WHEN TABLE 503 FOR AN A2
 OCCUPANCY, BUILDING TYPE III-B, HOW CODE COMPLIANCE WAS
 ACHIEVED WHEN ONLY 9,500 SQ. FT. IS ALLOWED? THE PLAN
 DOES NOT INDICATE THAT ANY INCREASES WERE TAKEN!
 1F) UNDER THE HEADING OF EARTHWORK THERE IS NO
 REQUIREMENT FOR SOILS TESTING. THIS AREA IS IN A
 QUESTIONABLE SOILS ZONE.
 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 2)SHEET 18F APPEARS TO BE THE LIFE SAFETY SHEET. PLEASE
 PROVIDE THE DOORWAYS THAT ARE TO BE THE MEANS OF
 EGRESS. SHEET 09-A THE ELEVATIONS APPEAR TO HAVE A SLAT
 SYSTEM OVER THE OPENINGS IN THE WALLS AND THE ONLY
 EGRESS FROM THE NEW ADDITION IS BACK THROUGH THE
 EXISTING BUILDING. SHOW THE OCCUPANT LOAD FOR THE
 EXISTING TENANT SPACE AS WELL AS THE ADDITION SHOW
 COMPLIANCE WITH;
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS:
 (7) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD NOTE RECEPTION IS NOT BUSINESS, SEE
 TABLE 1004.1.2 STANDING ONLY 5 NET
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 MINIMUM CONSTRUCTION TYPE
  
  
 3) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 ( E ) SHUTTERS
 (G) PRE-ENGINEERED A/C STANDS
  
 4) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5A) SHEET 07-A & 11-A BOTH SHOW THE USE OF W12X26
 I-BEAMS. SHEET 11-A INDICATES INFILL WITH (2) 2X12S AND
 ? INCH BOLTS. THE BOLT SPACING HAS NOT BEEN PROVIDED
 NOR THE DIAMETER OF THE HOLE IN THE STEEL.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 5B) THE OTHER ISSUE IS THE CONNECTION OF THE I-BEAM TO
 THE STEEL COLUMN, THE PLANS INDICATE A CONTINUOUS WELD,
 BUT THE TYPE OF WELD NOT PROVIDED. THIS WILL BE A SITE
 CONNECTION, PLEASE HAVE THE WELDERS CERTIFICATE ON SITE
 FOR INSPECTOR AT TIME OF INSPECTION. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
 THIS CONNECTION WILL BE PART OF THE MWFRS (MAIN WIND
 FORCE RESISTING SYSTEM.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  