| 2016-05-06 17:20:32 | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING. |
| | PERMIT #16041056 |
| | 5/6/16 |
| | |
| | 1) THE MECHANICAL PLANS FOR THE PROPOSED PROJECT DO NOT |
| | PROVIDE ENOUGH INFORMATION FOR PERMITTING. IN |
| | ACCORDANCE WITH SECTION 1009.1 FBC-14 EXISTING |
| | BUILDING, PLEASE PROVIDE THE FOLLOWING: |
| | A) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND |
| | SPACES PER TABLE 403.3 FBC-14 MECHANICALL. PROVIDE A |
| | SCHEDULE INDICATING THE REQUIRED AND PROVIDED CFM'S OF |
| | OUTDOOR AIR. PLEASE NOTE ALL AIR SUPPLIED TO INDOOR |
| | SMOKING LOUNGES SHALL BE EXHAUSTED AND SHALL NOT BE |
| | RE-CIRCULATED- SEE TABLE 403.3 FOOTNOTE B, AND SECTION |
| | 403.2.1 (3). |
| | B) AC COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | HUMIDOR SYSTEM PER SECTION C403.2.1 FBC-14 ENERGY |
| | CONSERVATION. |
| | C) AC EQUIPMENT SCHEDULES FOR ALL NEW AND EXISTING AC |
| | SYSTEMS. |
| | D) SUPPLY AND RETURN CFM'S AT ALL DIFFUSER AND RETURN |
| | GRILL LOCATIONS. |
| | E) AIR BALANCE CALCULATIONS- SEE SECTION 501.4 FBC-14 |
| | MECHANCIAL. |
| | F) AIR DEVICE SCHEDULE |
| | G) DUCT HANGING, SUPPORT, AND CONNECTION AND |
| | REINFORCEMENT DETAILS. |
| | H) CONDENSATE DISPOSAL DETAILS PER SECTION 307 |
| | I) WIND LOAD TIE-DOWN ENGINEERING FOR THE NEW ROOF TOP |
| | AC SYSTEM- SECTION 301.15. |
| | 2) CLARIFY WHY NO RETURN SYSTEMS ARE SHOWN FOR THE AC |
| | SYSTEMS SUPPLYING THE RETAIL AREA- SEE SECTION 601.5 |
| | FBC-=14 MECHANICAL. |
| | 3) PLEASE NOTE ADDITIONAL COMMENTS MAY FOLLOW AFTER |
| | CORRECTED PLANS ARE SUBMITTED. |
| | |