2016-05-06 17:20:321ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING.
 PERMIT #16041056
 5/6/16
  
 1) THE MECHANICAL PLANS FOR THE PROPOSED PROJECT DO NOT
 PROVIDE ENOUGH INFORMATION FOR PERMITTING. IN
 ACCORDANCE WITH SECTION 1009.1 FBC-14 EXISTING
 BUILDING, PLEASE PROVIDE THE FOLLOWING:
 A) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES PER TABLE 403.3 FBC-14 MECHANICALL. PROVIDE A
 SCHEDULE INDICATING THE REQUIRED AND PROVIDED CFM'S OF
 OUTDOOR AIR. PLEASE NOTE ALL AIR SUPPLIED TO INDOOR
 SMOKING LOUNGES SHALL BE EXHAUSTED AND SHALL NOT BE
 RE-CIRCULATED- SEE TABLE 403.3 FOOTNOTE B, AND SECTION
 403.2.1 (3).
 B) AC COOLING AND HEATING CALCULATIONS FOR THE NEW
 HUMIDOR SYSTEM PER SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
 C) AC EQUIPMENT SCHEDULES FOR ALL NEW AND EXISTING AC
 SYSTEMS.
 D) SUPPLY AND RETURN CFM'S AT ALL DIFFUSER AND RETURN
 GRILL LOCATIONS.
 E) AIR BALANCE CALCULATIONS- SEE SECTION 501.4 FBC-14
 MECHANCIAL.
 F) AIR DEVICE SCHEDULE
 G) DUCT HANGING, SUPPORT, AND CONNECTION AND
 REINFORCEMENT DETAILS.
 H) CONDENSATE DISPOSAL DETAILS PER SECTION 307
 I) WIND LOAD TIE-DOWN ENGINEERING FOR THE NEW ROOF TOP
 AC SYSTEM- SECTION 301.15.
 2) CLARIFY WHY NO RETURN SYSTEMS ARE SHOWN FOR THE AC
 SYSTEMS SUPPLYING THE RETAIL AREA- SEE SECTION 601.5
 FBC-=14 MECHANICAL.
 3) PLEASE NOTE ADDITIONAL COMMENTS MAY FOLLOW AFTER
 CORRECTED PLANS ARE SUBMITTED.
  