| Date |
Text |
| 2016-04-27 17:00:51 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | 1) SHEET 08 A - THERE IS NOTE INDICATING A FIREPIT BY |
| | SPECIALIST. |
| | |
| | THE FIREPIT SHALL BE SUBMITTED UNDER SEPARATE SHOP |
| | DRAWINGS IN COMPLIANCE WITH NFPA 1, CHAPTER 10, |
| | |
| | 10.11.8 INCINERATORS AND FIREPLACES. |
| | 10.11.8.1 INCINERATORS, OUTDOOR FIREPLACES, PERMANENT |
| | BARBECUES, AND GRILLS SHALL NOT BE BUILT, INSTALLED, OR |
| | MAINTAINED WITHOUT PRIOR APPROVAL OF THE AHJ. |
| | 10.11.8.2 INCINERATORS, OUTDOOR FIREPLACES, PERMANENT |
| | BARBECUES, AND GRILLS SHALL BE MAINTAINED IN GOOD |
| | REPAIR AND IN A SAFE CONDITION AT ALL TIMES. |
| | 10.11.8.3 OPENINGS IN INCINERATORS, OUTDOOR FIREPLACES, |
| | PERMANENT BARBECUES, AND GRILLS SHALL BE PROVIDED WITH |
| | AN APPROVED SPARK ARRESTER, SCREEN, OR DOOR. |
| | 10.11.9 OPEN-FLAME DEVICES. |
| | 10.11.9.1* WELDING TORCHES, TAR POTS, DECORATIVE |
| | TORCHES, AND OTHER DEVICES, MACHINES, OR PROCESSES |
| | LIABLE TO START OR CAUSE FIRE SHALL NOT BE OPERATED OR |
| | USED IN OR UPON ANY AREAS, EXCEPT BY PERMIT FROM THE |
| | AHJ. |
| | |
| | THE FLAME OF THE PIT SHALL BE PROTECTED AGAINST |
| | ACCIDENTAL AND/OR INTENTIONAL USE AND/OR MISUSE. |
| | |
| | IT IS IMPERATIVE FOR THE APPROVAL OF THIS DEVICE TO BE |
| | INSTALLED, SOMESORT OF DESIGN FEATURE SHALL BE |
| | INSTALLED TO PREVENT FLAME CONTACT WITH THE GENRAL |
| | PUBLIC. |
| | |
| | 2) SHEET 18 F - THERE IS A NOTE INDICATING FIRE |
| | SPRINKLER BY SPECIALIST. |
| | |
| | ANY AND ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER |
| | SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY |
| | CONTRACTORS. |
| | |
| | 3) SHEET 18 F - THE EXIT SIGN IN THE MIDDLE OF THE |
| | INTERIOR WALL SHALL BE MOVED TO THE AREA OF THE DOOR |
| | WAY LEADING TO THE CORRIDOR. |
| | |
| | 4) SHEET 18 F - THERE ARE NO EXIT SIGNS LOCATED IN THE |
| | TERRACE AREA. ADD AN EXIT SIGN AT EACH END OF THE |
| | TERRACE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |