Plan Review Notes
Plan Review Notes For Permit 16041056
Permit Number 16041056
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-04-27 17:00:51THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET 08 A - THERE IS NOTE INDICATING A FIREPIT BY
 SPECIALIST.
  
 THE FIREPIT SHALL BE SUBMITTED UNDER SEPARATE SHOP
 DRAWINGS IN COMPLIANCE WITH NFPA 1, CHAPTER 10,
  
 10.11.8 INCINERATORS AND FIREPLACES.
 10.11.8.1 INCINERATORS, OUTDOOR FIREPLACES, PERMANENT
 BARBECUES, AND GRILLS SHALL NOT BE BUILT, INSTALLED, OR
 MAINTAINED WITHOUT PRIOR APPROVAL OF THE AHJ.
 10.11.8.2 INCINERATORS, OUTDOOR FIREPLACES, PERMANENT
 BARBECUES, AND GRILLS SHALL BE MAINTAINED IN GOOD
 REPAIR AND IN A SAFE CONDITION AT ALL TIMES.
 10.11.8.3 OPENINGS IN INCINERATORS, OUTDOOR FIREPLACES,
 PERMANENT BARBECUES, AND GRILLS SHALL BE PROVIDED WITH
 AN APPROVED SPARK ARRESTER, SCREEN, OR DOOR.
 10.11.9 OPEN-FLAME DEVICES.
 10.11.9.1* WELDING TORCHES, TAR POTS, DECORATIVE
 TORCHES, AND OTHER DEVICES, MACHINES, OR PROCESSES
 LIABLE TO START OR CAUSE FIRE SHALL NOT BE OPERATED OR
 USED IN OR UPON ANY AREAS, EXCEPT BY PERMIT FROM THE
 AHJ.
  
 THE FLAME OF THE PIT SHALL BE PROTECTED AGAINST
 ACCIDENTAL AND/OR INTENTIONAL USE AND/OR MISUSE.
  
 IT IS IMPERATIVE FOR THE APPROVAL OF THIS DEVICE TO BE
 INSTALLED, SOMESORT OF DESIGN FEATURE SHALL BE
 INSTALLED TO PREVENT FLAME CONTACT WITH THE GENRAL
 PUBLIC.
  
 2) SHEET 18 F - THERE IS A NOTE INDICATING FIRE
 SPRINKLER BY SPECIALIST.
  
 ANY AND ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER
 SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 3) SHEET 18 F - THE EXIT SIGN IN THE MIDDLE OF THE
 INTERIOR WALL SHALL BE MOVED TO THE AREA OF THE DOOR
 WAY LEADING TO THE CORRIDOR.
  
 4) SHEET 18 F - THERE ARE NO EXIT SIGNS LOCATED IN THE
 TERRACE AREA. ADD AN EXIT SIGN AT EACH END OF THE
 TERRACE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  