Plan Review Notes
Plan Review Notes For Permit 16041056
Permit Number 16041056
Review Stop E
Sequence Number 1
Notes
Date Text
2016-05-05 07:08:06INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE REFERENCE ALL APPLICABLE FBC ENERGY
 CONSERVATION2014 5TH EDITION C405 REQUIREMENTS RELATED
 TO AUTOMATIC MEANS OF CONTROL FOR ALL LIGHTING.
 2. STATE ON DRAWINGS C405.7.4 COMPLETION
 REQUIREMENTS-(DRAWINGS AND MANUALS. SEE VERBIAGE IN THE
 CODE.
 3. PROVIDE A SHOW ON PLANS THE VOLTAGE DROP
 CALCULATIONS FOR FEEDER AND BRANCH CIRCUITS PER FBC EC
 C405.7 ELECTRICAL POWER MANDATORY
 4. ADDRESS ALL AND ANY FIRE DEPARTMENT COMMENTS RELATED
 TO THE ELECTRICAL SCOPE.
 5. LABEL THE ONE-LINE SERVICE RISER MAINS TO BE RATED
 FOR SERVICE ENTRANCE. A NOTE WILL SUFFICE.
 6. PROVIDE A GENERAL NOTE TO INDICATE NEC 110.16 ARC
 FLASH HAZARD WARNINGS- A NOTE WILL SUFFICE.
 7. PER NEC 110.24 A AND B. INDICATE ON PLANS REQUIRED
 FIELD MARKING OF THE AVAILABLE FAULT CURRENT DUE TO
 MODIFICATIONS.
 8. PLEASE CORRECT SERVICE CONDUCTORS SHOWN ON ONE-LINE
 RISER DIAGRAM FOR 225A SERVICE AT 2/0, SHOULD REFLECT
 4/0 PER TABLE OF AMPACITIES NEC 310.15B16
 9. SHOW SIZE OF THE GROUNDING ELECTRODE CONDUCTOR PER
 NEC 250.66
 10. PROVIDE NEUTRAL CALCULATIONS AS THE NEUTRAL IS
 BEING REDUCED AS SHOWN SERVICE CONDUCTORS. NEC 220.61B
 11. SHOW ON FLOOR PLAN THE LOCATION OF THE SERVICE
 EQUIPMENT. FBC 107.3.5
 12. PER NEC 230.2 YOU ARE SHOWING MULTIPLE SERVICES.
 PROVIDE A NOTE TO INDICATE PROPER SIGNAGE FOR FIRST
 RESPONDERS WITH IDENTIFICATION PER NEC 230.2E
 13. CLARIFY THE LOCATION OF THE MAIN CIRCUIT BREAKER A
 AND B. IS THE CONDUIT ROUTED UNDERGROUND? MAINS TO
 LOCATED AT THE NEAREST POINT OF ENTRANCE PER NEC 230
 14. CLARIFY SHOW WINDOW RECEPTACLE REQUIREMENTS FOR
 COMMERCIAL BUILDINGS PER NEC 220.43 NEC 210.62
 15. LABEL ON FLOOR PLAN ALL RECEPTACLE OUTLETS AT THE
 TERRACE LOCATION TO BE GFCI PROTECTED AND W/P PER NEC
 210.8B
 16. BAR AREA RECEPTACLES AND RECEPTACLE WITHIN 6FT OF
 MOP SINK TO LABELED GFCI PROTECTED. NEC 210.8B7
 17. DRINKING FOUNTAIN CIRCUIT A-8 TO BE A DEDICATED
 CIRCUIT AND LABELED GFCI PROTECTED. OTHER RECEPTACLES
 ON CIRCUIT A-8 TO BE REASSIGNED WITH OTHER CIRCUIT
 DESIGNATION. NEC 422.52
 18. DELETE GENERAL NOTES ON SHEETS 14 AND 15E THAT ARE
 NOT APPLICABLE TO THIS PROJECT. RESIDENTIAL NOTES.
 19. SHOW REQUIRED EXIT AND EMERGENCY LIGHTING FOR AREAS
 AND EGRESS DOORS. FBC 107.3.5
 20. SEPARATE PERMITS REQUIRED FOR ALL LOW VOLTAGE
 SYSTEMS AND FIRE ALARM. PROVIDE A NOTE
 21. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL.
 PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  