| Plan Review Notes For Permit 16040999 |
| Permit Number |
16040999 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-06 17:45:26 | | | | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE PROPOSED OCCUPANT LOAD AND USE FOR | | | SECOND FLOOR I UNDERSTAND ITS UNDER DIFFERENT PERMIT. | | | WPB AMEND. TO FBC SEC. 107.2.1 | | | | | | 2. SHT. LS 1.1 ON THE PLUMBING FIXTURE REQUIREMENT DOES | | | YOUR OCCUPANT LOAD INCLUDE SECOND FLOOR. WPB AMEND. TO | | | FBC SEC. 107.2.1 | | | | | | 3. SHT LS 1.1 YOU CALL OUT 7 TOILETS FOR MALE STUDENTS | | | I ONLY COUNT 6 INCLUDING 2ND FLOOR PLEASE CLARIFY. | | | 609.4 | | | | | | 4. SHT A-8.1 SHOW 16IN. MIN AND 18IN. MAX FROM SIDE | | | WALL TO CENTER OF TOILET COMPLY WITH 609.4 | | | | | | 5. SHT A-8.1 SHOW 33IN. MIN TO 36IN MAX MEASURED TO THE | | | TOP OF GRIPPING SURFACE ON THE GRAB BARS. FBC ACC. SEC. | | | 609.4 | | | | | | 6. SHT P 3.1 UP STREAM OF THE BACK TO BACK HANDICAP | | | TOILETS A HORIZONTAL DRY VENT IS NOT ALLOWED. PER FBC | | | PL 905.3 AND 4 | | | | | | 7. PROVIDE MANUFATURE SPEC SHEETS FOR OIL MINDER SUMP | | | PUMP AND WATER HEATERS. WPB AMEND. TO FBC SEC. 107.2.1 | | | | | | 8. PROVIDE STORM WATER RISER DIAGRAM WITH THE SQ FT. OF | | | AREA BEING DRAINED.WPB AMEND. TO FBC SEC. | | | 107.3.5.1.3(13) |
|