Plan Review Notes
Plan Review Notes For Permit 16040999
Permit Number 16040999
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-05-02 10:12:59THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 6.2 - THE DOOR SCHEDULE DOES NOT INCLUDE
 INDICATIONS TO DOORS IN SMOKE PARTITIONS.
  
 PLEASE PROVIDE DETAILS IN THE DOOR SCHEDULE INDICATING
 WHICH DOORS SHALL COMPLY WITH NFPA 101, CHAPTER 14,
 14.3.6 (A) & CHAPTER 8, 8.4. SMOKE PARTITIONS.
  
 2) SHEET A 6.2 - THE DOOR SCHEDULE DOES NOT INDICATE
 EXIT HARDWARE ON EXIT DOORS.
  
 PLEASE PROVIDE DETAILS IN THE DOOR SCHEDULE INDICATING
 WHICH DOORS SHALL COMPLY WITH NFPA 101, CHAPTER 7,
 MEANS OF EGRESS, 7.2.1.7 PANIC HARDWARE AND FIRE EXIT
 HARDWARE.
  
 3) SHEET A 1.1 - DOORS INDICATED AS 100 / 3 SHOW THEM
 OPENING INTO THE EXIT CORRIDOR.
  
 PER SECTION NFPA 101, DOOR SWING DIRECTION, 7.2.1.4.2,
 DOOR IS REQUIRED TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS.
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 PLEASE REVIEW AND PROVIDE INDICATIONS/DIMENSIONS
 COMPLYING WITH THE THE CODE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  