| 2016-04-28 10:43:56 | JOB PERMIT NUMBER: 16040999 |
| | JOB ADDRESS: 2823 AUSTRALIAN AVE |
| | WEST PALM BEACH FLORIDA |
| | DATE: APRIL 28 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - SHEET E1.1 NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. |
| | A 125 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HVAC EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED WITHIN 25 FT OF THE |
| | EQUIPMENT. MISSING FOR AC UNITS CU 1-3 , RTU 1-1 , QA 1 |
| | , RTU 1-2. |
| | - CLARIFY IF CIRCUIT L1A-9 IS A DRINKING FOUNTAIN ? IF |
| | SO IT SHALL BE PROTECTED WITH A GFCI. NEC 422.52 |
| | - SHEET E2.1 PENDANT LIGHTING OUTLET BOX IN THE CEILING |
| | SHALL BE REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A |
| | MINIMUM OF 50 LB. ADD THIS TO THE NOTES ON CEILING |
| | BOXES ON PAGE. |
| | - FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. |
| | - FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. A |
| | BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL |
| | CONNECTED LIGHTING POWER CALCULATED UNDER SECTION |
| | C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER |
| | CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING |
| | POWER DENSITY CHART TO SHOW COMPLIANCE. |
| | - SHEET E3.1 FIRE ALARM SHALL BE ON A SEPARATE PERMIT. |
| | - SHEET E4.1 PROVIDE AIC CALCS FOR EQUIPMENT AND |
| | INTERRUPTING RATING OF OCPD. NEC 110.10 , 110.9. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |