Plan Review Notes
Plan Review Notes For Permit 16040984
Permit Number 16040984
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-28 12:19:24JOB PERMIT NUMBER: 16040984
 JOB ADDRESS: 313 ARLINGTON RD
 WEST PALM BEACH FLORIDA
 DATE: APRIL 28 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - RISER DIAGRAM MISSING THE INTER-SYSTEM BONDING
 TERMINAL. FBC-R E3609.2
 - FBC-R E3902.12.13 - OUTLETS TO BE AFCI PROTECTED. (
 IF ANY MODIFICATIONS TO AREAS SUCH AS FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS,
 HALLWAYS, OR SIMILAR ROOMS )
 - FBC-R E4002.14 TAMPER-RESISTANT RECEPTACLES IN
 DWELLING UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL
 125-VOLT, 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER RESISTANT RECEPTACLES.
 - REFERENCE UNDERGROUND CLEARANCE REQUIRED PER FBC-R
 E3803.1.2 AND RED WARNING RIBBON FOR SERVICE CONDUCTORS
 AT LEAST 12 ? ABOVE LATERAL RACEWAY.
 - PANEL SCHEDULES REFLECT INCORRECT WATTAGE FOR RANGE
 4000 VA ? DRYER 2250 VA ? , A/C 5000 VA HOWEVER LOAD
 CALCS SHOWS 10000 VA FOR HEAT ? CLARIFY AND CORRECT
 ACCORDINGLY. FBC-R E3704.2.2
 - BATHROOMS REQUIRE A 20 AMP CIRCUIT OUTLET THAT SERVES
 NO OTHER LOAD UNLESS LIGHTING WITHIN THE SAME BATH IS
 ATTACHED TO GFCI RECEPTACLE. FBC-R E3703.4
 - NEW RECESSED LIGHTING SHALL BE 75 % HIGH EFFICIENCY ,
 IC RATED AND SEALED TO NOT COMPROMISE BUILDING THERMAL
 ENVELOPE. ( 2CFM ) FBC- E R 402.4.4 / 404.1.1
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011