| 2016-04-28 12:19:24 | JOB PERMIT NUMBER: 16040984 |
| | JOB ADDRESS: 313 ARLINGTON RD |
| | WEST PALM BEACH FLORIDA |
| | DATE: APRIL 28 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - RISER DIAGRAM MISSING THE INTER-SYSTEM BONDING |
| | TERMINAL. FBC-R E3609.2 |
| | - FBC-R E3902.12.13 - OUTLETS TO BE AFCI PROTECTED. ( |
| | IF ANY MODIFICATIONS TO AREAS SUCH AS FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUNROOMS, RECREATION ROOMS, CLOSETS, |
| | HALLWAYS, OR SIMILAR ROOMS ) |
| | - FBC-R E4002.14 TAMPER-RESISTANT RECEPTACLES IN |
| | DWELLING UNITS. IN ALL AREAS SPECIFIED IN 210.52, ALL |
| | 125-VOLT, 15 AND 20 AMPERE RECEPTACLES SHALL BE LISTED |
| | TAMPER RESISTANT RECEPTACLES. |
| | - REFERENCE UNDERGROUND CLEARANCE REQUIRED PER FBC-R |
| | E3803.1.2 AND RED WARNING RIBBON FOR SERVICE CONDUCTORS |
| | AT LEAST 12 ? ABOVE LATERAL RACEWAY. |
| | - PANEL SCHEDULES REFLECT INCORRECT WATTAGE FOR RANGE |
| | 4000 VA ? DRYER 2250 VA ? , A/C 5000 VA HOWEVER LOAD |
| | CALCS SHOWS 10000 VA FOR HEAT ? CLARIFY AND CORRECT |
| | ACCORDINGLY. FBC-R E3704.2.2 |
| | - BATHROOMS REQUIRE A 20 AMP CIRCUIT OUTLET THAT SERVES |
| | NO OTHER LOAD UNLESS LIGHTING WITHIN THE SAME BATH IS |
| | ATTACHED TO GFCI RECEPTACLE. FBC-R E3703.4 |
| | - NEW RECESSED LIGHTING SHALL BE 75 % HIGH EFFICIENCY , |
| | IC RATED AND SEALED TO NOT COMPROMISE BUILDING THERMAL |
| | ENVELOPE. ( 2CFM ) FBC- E R 402.4.4 / 404.1.1 |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |