Plan Review Notes
Plan Review Notes For Permit 16040977
Permit Number 16040977
Review Stop P
Sequence Number 4
Notes
Date Text
2017-01-19 04:45:52 
 1.) SHT. 5 OF 7 - THE PLANS SHOW TWO OF THE WATER
 SEVICES AS ONE INCH AND ALSO AS AN INCH AND A HALF.
 WHICH ONE IS IT? CLARIFY.
 2) SHOW THE CLEAR INSIDE DIMENSIONS (LXW) OF BOTH
 ACCESSIBLE TOILET ROOMS ON THE PLANS. WPB AMEND. TO FBC
 SEC. 107.2.1. 2ND REQUEST.
 3) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE LAVATORY
 IN EACH TOILET ROOM. COMPLY WITH 2014 FBC-ACCESS.
 SECS.305, & 606.2. 2ND REQUEST.
 4) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE DRINKING
 FOUNTAINS. COMPLY WITH 2014 FBC- ACCESS. SECS.211 &
 602.SUBMIT A DRINKING FOUNTAIN DETAIL FOR REVIEW.
 5) SHT. 5 OF 7 - THE PLANS SHOW THE SANITARY SEWER
 CROSSING THE WATER SERVICE. THIS IS A VIOLATION AND
 CANNOT REMAIN AS DESIGNED. COMPLY WITH 2014
 FBC-PLUMBING SECS. 603.2, 703.1.
 6) A BACKFLOW PREVENTION DEVICE IS REQUIRED FOR EACH
 BUILDING, NOT ONE FOR BOTH BUILDINGS. 2014 FBC -
 PLUMBING SECS. 608.1,
 7) DRINKING FOUNTAINS ARE NOT PERMITTED IN THE TOILET
 ROOMS PER 2014 FBC-PLUMBING SEC.410.4.
 8) SHT. 5 OF 7 SHOWS PVC PIPE SUPPLYING HOSE BIBBS.
 THIS BRANCH FOR THE HOSE BIBBS IS CONSIDERED PART OF
 THE WATER DISTRIBUTION SYSTEM AND PVC IS NOT PERMITTED
 FOR THIS USE PER 2014 FBC-PLUMBING SEC. 605.4 & TABLE
 605.4.
 9) SHTS. 3 & 4 OF 13 SHOW WHAT APPEARS TO BE A DRAIN
 LINE RUNNING THROUGH THE CENTER OF EACH BUILDING AND
 LABELED AS " 8 INCH PVC SCH. 40 FLOOR DRAIN" & "6 INCH
 PVC SCH. 40 FLOOR DRAIN" BUT NO FLOOR DRAINS ARE SHOWN.
 CLARIFY. SUBMIT A RISER DIAGRAM FOR THESE DRAINS AND
 SHOW THEM ON THE CIVIL DRAWINGS WHERE THEY EXIT THE
 BUILDING. FLOOR DRAINS SHALL BE EQUIPPED WITH TRAP
 PRIMERS. 2014 FBC-PLUMBING SEC.1002.4. WHAT WILL BE
 DISCHARGING INTO THESE LINES? CLARIFY.
 10) SHT. 13 OF 13 - ADA ELEVATIONS - THE GRAB BAR
 BEHIND THE WATER CLOSET SHALL COMPLY WITH FBC-ACCESS.
 SEC.604.5.2 AND FIGURE 604.5.2. 2ND REQUEST.
 11) NONE OF THE FIXTURES ARE VENTED ON THE SANITARY
 RISERS. COMPLY WITH 2014 FBC-PLUMBING SECS. 901.2,
 901.2.1.
 12) THERE IS A 2 INCH DRY VENT SHOWN ON THE SANITARY
 RISER. WHAT IS THIS VENT FOR? IT IS NOT TO CODE. COMPLY
 WITH 2014 FPC SEC. 905.3.
 13) SHT. 5 OF 7 - SOUTH BUILDING - THE LOCATION OF THE
 CLEANOUT IN THE BUILDING SEWER ON THE WEST SIDE IS
 INSTALLED IN THE OPPOSITE DIRECTION OF FLOW AND WASTE
 WILL COLLECT IN THIS AREA AS DESIGNED. 2014
 FBC-PLUMBING SEC. 708.5.
 14) SHOW WATER SERVICE AND HOSE BIBS ON FLOOR PLAN. PER
 WPB AMEND TO FBC 107.2.1
 15) SHT.13 OF 13 SHOWS THE HEIGHT OF THE TOILET PAPER
 DISPENSER AS 4'-9" ABOVE THE FINISH FLOOR. THE HEIGHT
 OF THE TOILET PAPER DISPENSER SHALL COMPLY WITH 2014
 FBC-ACCESS. SEC. 604.7.
 16) SHT. 3 OF 13 & SHT. 4 OF 13 - DRINKING FOUNTAIN BY
 COLUMN LINE E-1 AND A-1 - SHOW THE REQUIRED CLEAR FLOOR
 SPACE FOR THE DRINKING FOUNTAIN AND CLEARLY SHOW THE
 DRINKING FOUNTAIN AND SUBMIT AN ELEVATION DETAIL OF THE
 DRINKING FOUNTAIN. ONE DRINKING FOUNTAIN SHALL CCOMPLY
 WITH 2014 FBC- ACCESS. SECS.602.1 THROUGH 602.6 AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.7 OR A SINGLE
 DRINKING FOUNTAIN SHALL COMPLY WITH SECS.602.1 THROUGH
 602.6 AND 602.7. (HILO TYPE UNIT).
 17) THE PLANS SHOW A LAVATORY IN THE TOILET ROOMS WITH
 A 24 INCH BY 24 INCH VANITY. THE VANITY DOES NOT COMPLY
 WITH 2014 FBC-SEC.606.2. SHOW THE REQUIRED CLEAR FLOOR
 SPACE FOR THE LAVATORY. THE LAVATORY SHALL BE
 POSITIONED FOR A FORWARD APPROACH. 2014 FBC - ACCESS.
 SEC,606.2. THE CLEAR FLOOR SPACE SHALL BE CENTERED ON
 THE FFIXTURE.
 18) SHUTOFF VALVES ARE REQD. ON THE WATER RISER PER
 2014 FBC-PLUMBING SEC.606.2.
 19) HOSE BIBBS SHALL BE EQUIPPED WITH INDIVIDUAL
 SHUTOFF VALVES .2014 FBC-PLUMBING SEC..606.2 (2).
 20) FULL OPEN VALVES SHALL BE INSTALLED ON THE WATER
 DISTRIBUTION SYSTEM PER 2014 FBC-PLUMBING SEC.606.1.
 21) WHAT IS THE WALL AND FLOOR FINISH IN THE TOILET
 ROOMS? COMPLY WITH 2014 FBC-BUILDING SECS. 1210.2.1
 THROUGH 1210.2.4.
 22) SHTS. 3 & 4 OF 13 - THE WATER RISERS ONLY SHOW ONE
 DRINKING FOUNTAIN IN EACH BUILDING BUT THE FLOOR PLAN
 SHOWS TWO SEPARATE FOUNTAINS IN EACH BUILDING. CLARIFY.
 23) THE SANITARY RISERS DO NOT COMPLY WITH 2014
 FBC-PLUMBING SEC. 912.1 FOR FIXTURES PERMITTED ON A
 HORIZONTAL WET VENT.
 24) CLEANOUTS ARE REQUIRED IN THE BASE OF THE STACKS.
 2014 FBC-PLUMBING SEC.708.3.4.
 25) AN EMERGENCY SHOWER/EYEWASH STATION (PORTABLE)
 SHOULD BE CONSIDERED DUE TO THE NATURE OF THE
 OPERATIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW