2016-11-10 14:34:15BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040977
 ADD: 4510 GEORGIA AVE.
 CONT: OVERLAND CONSTRUCTION CO.
 TEL: 561-683-3210
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURS. NOV. 10/ 2016
 ACTION: DENIED
  
 1) CONTRACTOR: PLEASE PROVIDE 2 PERMIT APPLICATIONS
 SINCE THERE WILL BE 2 BUILDINGS BEING BUILT AT THE SAME
 TIME. SPIT THE ASSOCIATED COST TO REFLECT THE SQUARE
 FOOTAGE FOR EACH BUILDING. PLEASE NOTE THIS REQUEST IS
 FOR INSPECTION PURPOSES , TO BE ABLE TO KEEP RECORDS
 FOR BOTH THE NORTH BUILDING AND SOUTH BUILDING AS WELL
 AS FOR RECORD RETENTION PURPOSES.
 107.2.1. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 2)3RD REQUEST, NOTE 2 REPORTS SUBMITTED BOTH ARE
 COPIES. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 EFFECTIVE DATE 05/06/2009. (2)(A) EVERY SHEET OF PLANS
 AND PRINTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY
 THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
  
 1ST ROUND OF COMMENTS. THIS REVIEW THERE HAS BEEN NO
 SOILS REPORT SUBMITTED FOR THIS SITE. 2014 FBC-B
 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION,
 STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR
 WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED
 IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 3) 3RD REQUEST. THE COVERSHEET SHOWS BUILD TYPE AS A 5B
 AND AN F2 OCCUPANCY. OCCUPANTS LOADS:
 NORTH BUILDING 3394/ 100 (F2 TABLE 1004.1.2.)= 4
 OCCUPANTS.
 SOUTH BUILDING 4248/100 (F2 TABLE 1004.1.2.)= 5
 OCCUPANTS.
 PLEASE MAKE CORRECTIONS.
  
 4)3RD ROUND COMMENT. NOTICE TO CONTRACTOR. THE DESIGNER
 OF RECORD IT APPEARS WOULD LIKE THIS PERMIT TO BE A
 STRUCTURE ONLY PERMIT TO GET THE BUILDINGS STARTED. WE
 HAVE NOT SEEN THE COMPONENTS AND CLADDING FOR THE
 BUILDING (WALLS AND ROOFING) SO THE BUILDING PERMIT
 CANNOT BE ISSUED BUT WITH THE SCOPE OF THE PERMIT BEING
 A STRUCTURE ONLY PERMIT THE FEES TRANSFERRED FOR THE
 STRUCTURE ONLY IT MAY BE ABLE TO GET THE PERMIT OUT
 EARLIER.
 1ST ROUND COMMENT. SHEET 12 OF 13 WILL NEED TO SHOW
 COMPLIANCE WITH 2014 FBC-ENERGY CODE 402.1 C402.1
 GENERAL (PRESCRIPTIVE). THE BUILDING THERMAL ENVELOPE
 SHALL COMPLY WITH SECTION C402.1.1. SECTION C402.1.2
 SHALL BE PERMITTED AS AN ALTERNATIVE TO THE R-VALUES
 SPECIFIED IN SECTION C402.1.1.
  
 5-6) COMPLIED RESIDENT INSPECTOR.
  
 7A) COMPLIED. RESIDENT INSPECTOR FORMS MUST BE SIGNED
 BY ALL PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT. FORMS WERE E-MAILED TO:
 [email protected] 5/17/16 03:03PM.
  
 7B) 3RD REQUEST. FOR THE RESIDENT INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME. '
  
 7C) 3RD REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 7D) 3RD REQUEST. FOR ALL RESIDENT INSPECTOR BUILDINGS 3
 SETS OF DOCUMENTS ARE REQUIRED PLANS SHOP DRAWINGS AND
 PRODUCT APPROVALS.
  
 7E) NOTICE ONLY NO ACTION REQUIRED AT THIS TIME. PLEASE
 CALL THE CITY OF WEST PALM BEACHS AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR IN-PROGRESS
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS AS WELL
 AS KEEPING THE PERMIT ALIVE (CURRENT) INSPECTIONS
 WITHIN A 6 MONTH PERIOD.
  
 8A) 3RD REVIEW CYCLE TO DATE NO PRODUCT APPROVALS HAVE
 BEEN SUBMITTED FOR THE ROOF OR WALL SYSTEMS.
  
 1ST REVIEW COMMENTS. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. SUBMITTED NOA 13-1217.16
 EXPIRED.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, METAL PANEL WALL SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES METAL ROOFING
 PANELS
 (E) SHUTTERS
 (G) PRE-ENGINEERED A/C STANDS
  
  
 8B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9) 3RD REQUEST. SHEET 2 O 13 INDICATES THE WIND DESIGN
 CRITERIA IS NOT GIVEN THE ASSOCIATED PRESSURES ARE
 GIVEN.
 WINDOW AND DOOR PRESSURES ARE LISTED AS +30,4/ -33.5
 BUT THE SQUARE FOOTAGE OF THE OPENING IS NOT GIVEN. THE
 PRESSURES APPEAR TO BE FOR EXPOSURE B, 10 SQ. FT. 15
 FT. MEAN ROOF HEIGHT.
 THE ROOF PRESSURES IN ROOF ZONE 1 APPEAR TO BE IN VULT
 AND THE PRESSURES IN ZONES 2 & 3 APPEAR TO BE IN VASD.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 10A-C) SEMI-COMPLIED, THE COLD-FORMED STEEL LIGHT-FRAME
 BUILDING SUBMITTED DEAN STEEL BUILDING SHOP DRAWINGS
 AND CONSTRUCTION STANDARDS. NO PRODUCT APPROVALS FOR
 THE ROOF AND WALL PANELS.
 10D) 3RD REQUEST. TO DATE THERE HAS BEEN ROOFING NOR
 WALL PANEL PRODUCT APPROVALS SUBMITTED. 2211.5 FLOOR
 AND ROOF SYSTEM DESIGN. FRAMING FOR FLOOR AND ROOF
 SYSTEMS IN BUILDINGS SHALL BE DESIGNED IN ACCORDANCE
 WITH EITHER AISI S210 OR AISI S100.
 2007AISI S100 D6.2.1(A) STRENGTH (RESISTANCE) OF
 STANDING SEAM ROOFING PANEL SYSTEM. PROVIDE
 CALCULATIONS FOR THE ROOFING AND WALL PANEL SYSTEMS.
 IDENTIFY WHICH SYSTEM IS BEING INSTALLED AND GAUGE OF
 THE MATERIAL.
  
  
 10E) COMPLIED. 2211.6 LATERAL DESIGN. LIGHT-FRAME SHEAR
 WALLS, DIAGONAL STRAP BRACING .
  
 11-12) COMPLIED ACCESSIBLE RESTROOM.
 .
  
 13) COMPLIED. ACCESSIBLE STALL PARKING SPACE. ADVISORY
 502.3.3 MARKING.
 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  