Plan Review Notes For Permit 16040977
Permit Number 16040977
Review Stop P
Sequence Number 3
Notes
Date Text
2016-11-20 03:17:023RD REVIEW
 PLUMBING COMMENTS:
  
 1. SHOW THE WATER SERVICES AND SEWER LINES ON THE CIVIL
 DRAWING. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE OCCUPANCY IS NOTED AS AN F-2 ON THE PLANS.
 INDICATE ON BOTH SETS OF PLANS THE TYPE OF OPERATIONS
 THAT WILL BE CONDUCTED IN THIS FACILITY. WPB AMEND. TO
 FBC SEC. 107.2.1, 2014 FBC SEC. 302.1.
 3) SHOW THE CLEAR INSIDE DIMENSIONS (LXW) OF BOTH
 ACCESSIBLE TOILET ROOMS ON THE PLANS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 4) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER
 CLOSET AND THE LAVATORY IN EACH TOILET ROOM. COMPLY
 WITH 2014 FBC-ACCESS. SECS.604.3.1 & 606.
 5) PAGE 4 OF 13 HAS A NOTE THAT READS "RISER CAP AT
 FLOOR, 3 INCH STUB OUT FOR FUTURE BATHROOM." SUBMIT A
 SANITARY DIAGRAM FOR THIS FUTURE LINE ON THE PLANS AND
 THE TERMINATION POINT WHERE IT CONNECTS TO THE SEWER
 SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1.
 6) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED IN
 EACH BUILDING PER 2014 FPC TABLE 403.1 FOOTNOTE # E AND
 2014 FBC-ACCESS. SEC. 211.2.
 7) A SERVICE SINK IS REQUIRED IN EACH BUILDING PER
 TABLE 403.1 OF 2014 FPC.
 8) PROVIDE A WATER RISER DIAGRAM FOR EACH BUILDING FOR
 REVIEW. WPB AMEND TO FBC 107.3.5.1.3 (11).
 9) TOILET PAPER DISPENSERS SHALL COMPLY WITH
 FBC-ACCESS. SECS. 309.4 AND 604.7.AND SHALL BE 7 INCHES
 (180 MM) MINIMUM AND 9 INCHES (230 MM) MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES (380 MM) MINIMUM AND 48 INCHES (1220 MM) MAXIMUM
 ABOVE THE FINISH FLOOR AND SHALL NOT BE LOCATED BEHIND
 GRAB BARS.
 10) THE GRAB BAR BEHIND THE WATER CLOSET SHALL COMPLY
 WITH FBC-ACCESS. SEC.604.5.2 AND FIGURE 604.5.2.
 11) SIZE ALL SECTIONS OF THE SANITARY RISER.
 12) THERE IS A 2 INCH DRY VENT SHOWN ON THE SANITARY
 RISER. WHAT IS THIS VENT FOR? IT IS NOT TO CODE. COMPLY
 WITH 2014 FPC SEC. 905.3.
 13) SHOW BUILDING DRAIN AND SEWER ON FLOOR PLAN. PER
 WPB AMEND TO FBC 107.2.1.
 14) SHOW WATER SERVICE AND HOSE BIBS ON FLOOR PLAN. PER
 WPB AMEND TO FBC 107.2.1
 15) SHT.13 OF 13 SHOWS THE HEIGHT OF THE TOILET PAPER
 DISPENSER AS 4'-9" ABOVE THE FINISH FLOOR. THE HEIGHT
 OF THE TOILET PAPER DISPENSER SHALL COMPLY WITH 2014
 FBC-ACCESS. SEC. 604.7.
 16) A CLEANOUT SHALL BE INSTALLED AT THE JUNCTION OF
 THE BUILDING DRAIN AND THE BUILDING SEWER OF EACH
 BUILDING PER 2014 FPC SEC. 708.3.5. THIS WILL ALSO
 APPLY TO THE FUTURE LINE FOR THE SOUTH BUILDING.
 ANOTHER CLEANOUT BROUGHT TO GRADE SHALL BE INSTALLED
 WHERE THE BUILDING SEWER CONNECTS TO THE CITY LATERAL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  