2016-11-08 13:30:232ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16040977
 11/8/16
  
 1) LLOYDS INDUSTRY LOUVERS ARE SPECIFIED FOR THE
 BUILDINGS ON SHEET 7. PLEASE SUBMIT: A) MANUFACTURER'S
 SPECIFICATIONS FOR THE LOUVERS THAT VERIFY AMCA 550
 COMPLIANCE- SEE SECTION 401.5. B) A MIAMI-DADE NOA
 AND/OR A FLORIDA PRODUCT APPROVAL.
  
 2) REFER TO SECTION C101.4.8 FBC-14 ENERGY
 CONSERVATIONS. IF THE PROPOSED BUILDING DOES NOT MEET
 ANY OF THE EXEMPTIONS LISTED IN THE SUB-SECTIONS UNDER
 C101.4.8 THEN ENERGY CONSERVATION COMPLIANCE IS
 REQUIRED PER SECTION C101.2. PLEASE SEE SECTION C401.2
 FOR COMPLIANCE PATH OPTIONS.
  
 3) THE APPLICATION INDICATES A NEW WAREHOUSE BUILDING
 WHICH CAN EITHER BE AN S-1 OR S-2 OCCUPANCY PER SECTION
 311 FBC-14 BUILDING. THE PLANS HOWEVER, ON SHEET 1
 INDICATE AN F-2 FACTORY OCCUPANCY. FACTORIES GENERALLY
 HAVE EMPLOYEES AND EQUIPMENT FOR PRODUCTION INSTALLED,
 HOWEVER THE PLANS SHOW NONE OF THESE. PLEASE SEE
 SECTION 309.1: MINIMUM HEATING IS REQUIRED FOR OCCUPIED
 SPACES. REVISE THE PLAN TO PROVIDE COMPLETE DETAILS AND
 INFORMATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER