| Plan Review Notes For Permit 16040977 |
| Permit Number |
16040977 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-11-08 13:30:23 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16040977 | | | 11/8/16 | | | | | | 1) LLOYDS INDUSTRY LOUVERS ARE SPECIFIED FOR THE | | | BUILDINGS ON SHEET 7. PLEASE SUBMIT: A) MANUFACTURER'S | | | SPECIFICATIONS FOR THE LOUVERS THAT VERIFY AMCA 550 | | | COMPLIANCE- SEE SECTION 401.5. B) A MIAMI-DADE NOA | | | AND/OR A FLORIDA PRODUCT APPROVAL. | | | | | | 2) REFER TO SECTION C101.4.8 FBC-14 ENERGY | | | CONSERVATIONS. IF THE PROPOSED BUILDING DOES NOT MEET | | | ANY OF THE EXEMPTIONS LISTED IN THE SUB-SECTIONS UNDER | | | C101.4.8 THEN ENERGY CONSERVATION COMPLIANCE IS | | | REQUIRED PER SECTION C101.2. PLEASE SEE SECTION C401.2 | | | FOR COMPLIANCE PATH OPTIONS. | | | | | | 3) THE APPLICATION INDICATES A NEW WAREHOUSE BUILDING | | | WHICH CAN EITHER BE AN S-1 OR S-2 OCCUPANCY PER SECTION | | | 311 FBC-14 BUILDING. THE PLANS HOWEVER, ON SHEET 1 | | | INDICATE AN F-2 FACTORY OCCUPANCY. FACTORIES GENERALLY | | | HAVE EMPLOYEES AND EQUIPMENT FOR PRODUCTION INSTALLED, | | | HOWEVER THE PLANS SHOW NONE OF THESE. PLEASE SEE | | | SECTION 309.1: MINIMUM HEATING IS REQUIRED FOR OCCUPIED | | | SPACES. REVISE THE PLAN TO PROVIDE COMPLETE DETAILS AND | | | INFORMATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|