| 2016-11-03 10:38:53 | JOB PERMIT NUMBER: 16040977 |
| | JOB ADDRESS: 4510 GEORGIA |
| | WEST PALM BEACH FLORIDA |
| | DATE: NOVEMBER 3, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| | AMENDMENTS. PREVIOUS ELECTRICAL COMMENTS HAVE BEEN |
| | ADDRESSED HOWEVER; PLEASE SEE BELOW A LIST OF NEW ITEMS |
| | NOTED. |
| | |
| | 1] CLARIFY IF EMERGENCY LIGHTS ARE COMBO EXIT LIGHTS AS |
| | WELL AND RE-CONFIGURE ELECTRICAL LEGEND SCHEDULE TO |
| | CORRELATE FLOOR PLAN SYMBOL. FBC-1011 EXIT LIGHT |
| | REQUIRED (SHOW COMPLIANCE). |
| | |
| | 2] SOUTH BUILDING ELECTRICAL RISER DIAGRAM SHOWS A 250 |
| | AMP FUSE DISCONNECT PROTECTING A 200 AMP PANELBOARD. |
| | THIS IS A VIOLATION OF NEC 408.36 WHICH STATES THAT THE |
| | PANELBOARD SHALL BE PROTECTED BY AN OVERCURRENT |
| | PROTECTIVE DEVICE NOT GREATER THAN THAT OF THE |
| | PANELBOARD BUS RATING. PLEASE CORRECT ACCORDINGLY. |
| | |
| | 3] PROVIDE FPL AVAILABLE FAULT CURRENT LETTER AND |
| | DEMONSTRATE AIC CALCULATIONS TO VERIFY SHORT CIRCUIT |
| | RATINGS OF THE ELECTRICAL EQUIPMENT. NEC 110.24, |
| | 110.10, 110.9 (SHOW COMPLIANCE) |
| | |
| | 4] ADD A BLOCK NOTE FOR THE ARC-FLASH HAZARD WARNING |
| | LABEL ON ELECTRICAL EQUIPMENT LIKELY TO REQUIRE SERVICE |
| | WHILE ENERGIZED. THE FIELD MARK SHALL BE SUITABLE FOR |
| | THE ENVIRONMENT INVOLVED PER NEC 110.16. |
| | |
| | - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| | DIRECTLY. |
| | |
| | 3RD REVIEW FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 561-805-6713 |
| | [email protected] |
| | |