2016-08-05 15:36:032ND REVIEW FBC-2014 MECHANICAL
 PERMIT #1604097
 8/5/16
  
 1) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS. I AM
 REPRINTING IT BELOW. PLEASE NOTE IT IS THE ENGINEER OF
 RECORD'S RESPONSIBILITIY TO EITHER DESIGN OR APPROVE A
 DESIGN FOR THE VENTILATION SYSTEMS, NOT THE SHELL
 CONTRACTOR AS THE RESPONSE NARRATIVE IS STATING.
  
 2) INDICATE HOW THE BUILDING WILL BE VENTILATED-
 NATURALLY OR MECHANICALLY. FOR NATURAL VENTILATION SEE
 SECTION 402, AND PROVIDE A CALCULATION PER SECTION
 402.2. FOR MECHANICAL VENTILATION SEE TABLE 403.3 AND
 PROVIDE CALCULATIONS AND A SCOPE OF WORK WITH
 CORREPONDING DRAWINGS AND DETAILS. PLEASE NOTE FOR
 ENCLOSED PARKING GARAGES SEE SECTION 404 FBC-14
 MECHANICAL, AND FOR MOTOR VEHICLE REPAIR GARAGES SEE
 406.8 FBC-14 BUILDING.
  