2016-04-27 07:16:031ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040977
 4/27/16
  
 1) PROVIDE EXHAUST VENTILATION FOR THE NEW TOILET ROOM
 PER TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A FAN
 SCHEDULE, INDICATE THE TYPE AND SIZE OF EXHAUST DUCT,
 SHOW THE DUCT RUN AND TERMINATION LOCATION.
 2) INDICATE HOW THE BUILDING WILL BE VENTILATED-
 NATURALLY OR MECHANICALLY. FOR NATURAL VENTILATION SEE
 SECTION 402, AND PROVIDE A CALCULATION PER SECTION
 402.2. FOR MECHANICAL VENTILATION SEE TABLE 403.3 AND
 PROVIDE CALCULATIONS AND A SCOPE OF WORK WITH
 CORREPONDING DRAWINGS AND DETAILS. PLEASE NOTE FOR
 ENCLOSED PARKING GARAGES SEE SECTION 404, AND FOR MOTOR
 VEHICLE REPAIR GARAGES SEE 406.8 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER