| Plan Review Notes For Permit 16040977 |
| Permit Number |
16040977 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-27 07:16:03 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16040977 | | | 4/27/16 | | | | | | 1) PROVIDE EXHAUST VENTILATION FOR THE NEW TOILET ROOM | | | PER TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A FAN | | | SCHEDULE, INDICATE THE TYPE AND SIZE OF EXHAUST DUCT, | | | SHOW THE DUCT RUN AND TERMINATION LOCATION. | | | 2) INDICATE HOW THE BUILDING WILL BE VENTILATED- | | | NATURALLY OR MECHANICALLY. FOR NATURAL VENTILATION SEE | | | SECTION 402, AND PROVIDE A CALCULATION PER SECTION | | | 402.2. FOR MECHANICAL VENTILATION SEE TABLE 403.3 AND | | | PROVIDE CALCULATIONS AND A SCOPE OF WORK WITH | | | CORREPONDING DRAWINGS AND DETAILS. PLEASE NOTE FOR | | | ENCLOSED PARKING GARAGES SEE SECTION 404, AND FOR MOTOR | | | VEHICLE REPAIR GARAGES SEE 406.8 FBC-14 BUILDING. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|