| 2016-04-28 13:10:38 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET 1 OF 13 - THERE IS NO REFERNCE TO THE |
| | COMPLIANCE WITH THE CURRENT FIRE CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | |
| | PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE. |
| | |
| | 2) SHEET 1 OF 13 - THERE IS NO INDICATION OF THE |
| | OCCUPANCY CLASSIFICATION THAT THIS PROJECT WILL BE |
| | BUILT IN COMPLAINCE WITH. PLEASE PROVIDE THE APPLICABLE |
| | OCCUPANCY CLASSIFICATION PER THE FLORIDA FIRE |
| | PREVENTION CODE. |
| | |
| | 3) SHEET 7 & 8 OF 13 - PER FLORIDA 69A-60.0081; NOTICE |
| | SIGNAGE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR |
| | ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR |
| | MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| | WITH A MALTESE CROSS SIGN MEASURING 8 INCHES |
| | HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED |
| | REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED |
| | WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | PROVIDE A NOTE INDICATING THE POSTING OF A ROOF SIGN. |
| | |
| | 4) SHEET 9 OF 13 - THERE IS NO INDICATION OF EMERGENCY |
| | LIGHTING. PROVIDE EMERGECNY LIGHTING PER NFPA 101, |
| | CHAPTER 40. |
| | |
| | 40.2.9 EMERGENCY LIGHTING |
| | 40.2.9.1 EMERGENCY LIGHTING SHALL BE PROVIDED IN |
| | ACCORDANCE WITH SECTION 7.9, EXCEPT AS OTHERWISE |
| | EXEMPTED BY 40.2.9.2. |
| | 40.2.9.2 EMERGENCY LIGHTING SHALL NOT BE REQUIRED FOR |
| | ANY OF THE FOLLOWING: |
| | (1) SPECIAL-PURPOSE INDUSTRIAL OCCUPANCIES WITHOUT |
| | ROUTINE HUMAN HABITATION |
| | (2) STRUCTURES OCCUPIED ONLY DURING DAYLIGHT HOURS, |
| | WITH SKYLIGHTS OR WINDOWS ARRANGED TO PROVIDE THE |
| | REQUIRED LEVEL OF ILLUMINATION ON ALL PORTIONS OF THE |
| | MEANS OF EGRESS DURING SUCH HOURS. |
| | |
| | 7.9.1.2 FOR THE PURPOSES OF 7.9.1.1, EXIT ACCESS SHALL |
| | INCLUDE ONLY DESIGNATED STAIRS, AISLES, CORRIDORS, |
| | RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING TO AN EXIT. |
| | FOR THE PURPOSES OF 7.9.1.1, EXIT DISCHARGE SHALL |
| | INCLUDE ONLY DESIGNATED STAIRS, RAMPS, AISLES, |
| | WALKWAYS, AND ESCALATORS LEADING TO A PUBLIC WAY. |
| | |
| | 7.9.2 PERFORMANCE OF SYSTEM. |
| | 7.9.2.1* EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A |
| | MINIMUM OF 1? HOURS IN THE EVENT OF FAILURE OF NORMAL |
| | LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE |
| | ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT |
| | LESS THAN AN AVERAGE OF 1 FT-CANDLE (10.8 LUX) AND, AT |
| | ANY POINT, NOT LESS THAN 0.1 FT-CANDLE (1.1 LUX), |
| | MEASURED ALONG THE PATH OF EGRESS AT FLOOR LEVEL. |
| | ILLUMINATION LEVELS SHALL BE PERMITTED TO DECLINE TO |
| | NOT LESS THAN AN AVERAGE OF 0.6 FT-CANDLE (6.5 LUX) |
| | AND, AT ANY POINT, NOT LESS THAN 0.06 FT-CANDLE (0.65 |
| | LUX) AT THE END OF 1? HOURS. A MAXIMUM-TO-MINIMUM |
| | ILLUMINATION UNIFORMITY RATIO OF 40 TO 1 SHALL NOT BE |
| | EXCEEDED. |
| | |
| | 5) SHEET 10 OF 13 - THE ARRANGEMENT OF EXIT/EGRESS DOES |
| | NOT APPEAR TO COMPLY WITH NFPA 101, CHAPTER 40, 40.2.5 |
| | |
| | 40.2.5 ARRANGEMENT OF MEANS OF EGRESS. MEANS OF EGRESS, |
| | ARRANGED IN ACCORDANCE WITH SECTION 7.5, SHALL NOT |
| | EXCEED THAT PROVIDED BY TABLE 40.2.5. |
| | |
| | THE TABLES INDICATES 50FT. |
| | |
| | PLEASE REVIEW AND PROVIDED FOR COMPLIANCE. |
| | |
| | 6) SHEET 13 OF 13 - THERE IS NO DOOR SSCHEDULE |
| | INDICATED. PLEASE PROVIDE A DOOR SCHEDULE THAT INCLUDES |
| | HAREWARE AND LOCKS COMPLYING WITH NFPA 101, CHAPTER 7. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |