Plan Review Notes
Plan Review Notes For Permit 16040977
Permit Number 16040977
Review Stop E
Sequence Number 1
Notes
Date Text
2016-05-04 20:03:101ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. NEC 600.5 REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE 20 AMP
 DEDICATED OUTLET IN AN ACCESSIBLE LOCATION AT EACH
 ENTRANCE TO EACH TENANT SPACE FOR SIGN OR OUTLINE
 LIGHTING. SIGN OUTLET MISSING ON EACH OF THE FOUR
 DOORS.
 2. NEC 422.31. PERMANENTLY CONNECTED APPLIANCE OF OVER
 300 VA OR 1/8 HP REQUIRES A DISCONNECT WITHIN SIGHT OF
 THE APPLIANCE. DISCONNECTS REQUIRED FOR THE TANKLESS
 WATER HEATERS.
 3. NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20
 AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET
 LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF
 WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL
 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING
 RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE
 ?WR?.
 4. NEC 408.4 CIRCUIT DIRECTORY REQUIRED. YOU SHALL
 SUBMIT SITE SPECIFIC PANEL SCHEDULES.
 5. NEC 215.5 YOU SHALL PROVIDE SITE SPECIFIC LOAD CALCS
 ALONG WITH THE RISER DIAGRAM.
 6. FBC-B1006.1 MEANS OF EGRESS ILLUMINATION REQUIRED.
 THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE,
 SHALL BE ILLUMINATED AT ALL TIMES THE BUILDING SPACE
 SERVED BY THE MEANS OF EGRESS ARE OCCUPIED. THIS HOLDS
 TRUE NOT ONLY FOR THE INTERIOR SPACE BUT FOR THE MEANS
 OF EGRESS MENTIONED LATER WITH PARKING LOT
 ILLUMINATION.
 7. FBC-E C405.2.2. PROVIDE AUTOMATIC LIGHTING SHUTOFF
 AS REQUIRED BY CODE.
 8. FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS.
 A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE. THIS APPLIES TO
 BOTH BLDGS. PROVIDE A LIGHTING POWER DENSITY CHART.
 9. YOUR NOTES MENTION AN ABSTRACT REFERENCE TO THE
 CURRENT CODE. YOU SHALL INCLUDE THE APPLICABLE CODE ON
 THE PLANS.
 10. YOUR NOTE B MAKES REFERENCE TO THE FBC- ENERGY BUT
 THE FLOOR PLAN DOES NOT SHOW OR MEET THE REQUIREMENTS.
 11. YOU WILL NEED TO COMPLY WITH THE CITY AMENDMENTS
 FOR PARKING LOT LIGHTING AND THE ENERGY CODE
 REQUIREMENTS FOR SAME.
 12. DECIDE WHERE WILL THE PARKING LOT LIGHTING BE
 POWERED FROM. DECIDE IF THERE WILL BE A HOUSE PANEL OR
 WILL THE LOAD BE EVENLY DIVIDED AMONGST THE BLDGS.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  