| Date |
Text |
| 2016-05-17 15:28:32 | |
| | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16040977 |
| | ADD: 4510 GEORGIA AVE. |
| | CONT: OVERLAND CONSTRUCTION CO. |
| | TEL: 561-683-3210 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MAY 17/2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE 2 PERMIT APPLICATIONS SINCE THERE |
| | WILL BE 2 BUILDINGS BEING BUILT AT THE SAME TIME. SPIT |
| | THE ASSOCIATED COST TO REFLECT THE SQUARE FOOTAGE FOR |
| | EACH BUILDING. PLEASE NOTE THIS REQUEST IS FOR |
| | INSPECTION PURPOSES , TO BE ABLE TO KEEP RECORDS FOR |
| | BOTH THE NORTH BUILDING AND SOUTH BUILDING AS WELL AS |
| | FOR RECORD RETENTION PURPOSES. |
| | 107.2.1. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| | |
| | 2) THIS REVIEW THERE HAS BEEN NO SOILS REPORT SUBMITTED |
| | FOR THIS SITE. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. |
| | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 3) SHEET 2 OF 13 HAS THE WIND DESIGN CRITERIA BUT NO |
| | OTHER PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| | TABLE 503). |
| | FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE |
| | THE FOLLOWING COMPONENTS: |
| | NOTE FBC-B TABLE 602 5 FT TO 10FT FOR ALL OCCUPANCIES |
| | EXCEPT H WILL REQUIRE 1 HOUR FIRE RATING, H OCCUPANCY |
| | REQUIRES 2 HOUR FIRE RATING. |
| | FIRE-RESISTANT SEPARATIONS |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | WIND REQUIREMENTS |
| | BUILDING ENVELOPE |
| | STRUCTURAL CALCULATIONS (STEEL BUILDING) |
| | |
| | 4) SHEET 12 OF 13 WILL NEED TO SHOW COMPLIANCE WITH |
| | 2014 FBC-ENERGY CODE 402.1 C402.1 GENERAL |
| | (PRESCRIPTIVE). THE BUILDING THERMAL ENVELOPE SHALL |
| | COMPLY WITH SECTION C402.1.1. SECTION C402.1.2 SHALL BE |
| | PERMITTED AS AN ALTERNATIVE TO THE R-VALUES SPECIFIED |
| | IN SECTION C402.1.1. |
| | |
| | 5) PLEASE NOTE THIS IS A STEEL BOLTABLE BUILDING THAT |
| | WILL REQUIRE A RESIDENT INSPECTOR. 110.3.9 OTHER |
| | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR |
| | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED |
| | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT |
| | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING |
| | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY |
| | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| | (7). FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION |
| | |
| | SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| | WORK IS UNDERWAY ON THE STRUCTURAL |
| | ELEMENTS OF THE BUILDING. SUCH INSPECTORS SHALL BE A |
| | REGISTERED ARCHITECT, OR ENGINEER, OR A |
| | PERSON LICENSED UNDER CHAPTER 468, PART XII, FLORIDA |
| | STATUTES. SUCH INSPECTORS SHALL SUBMIT |
| | WEEKLY PROGRESS REPORTS INCLUDING THE DAILY INSPECTIONS |
| | TO THE BUILDING OFFICIAL, AND INCLUDING A |
| | CODE COMPLIANCE OPINION OF THE RESIDENT INSPECTOR. |
| | |
| | 7A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL |
| | PARTIES NOTARIZED AND RETURNED TO THE BUILDING |
| | DEPARTMENT. FORMS WERE E-MAILED TO: |
| | [email protected] 5/17/16 03:03PM. |
| | |
| | 7B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME. ' |
| | |
| | 7C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 7D) FOR ALL RESIDENT INSPECTOR BUILDINGS 3 SETS OF |
| | DOCUMENTS ARE REQUIRED PLANS SHOP DRAWINGS AND PRODUCT |
| | APPROVALS. |
| | |
| | 7E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS AS WELL AS KEEPING THE PERMIT ALIVE |
| | (CURRENT) INSPECTIONS WITHIN A 6 MONTH PERIOD. |
| | |
| | 8A) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. SUBMITTED NOA 13-1217.16 |
| | EXPIRED. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, METAL PANEL WALL SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES METAL ROOFING |
| | PANELS |
| | (E) SHUTTERS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | |
| | 8B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 9) SHEET 2 O 13 INDICATES THE WIND DESIGN CRITERIA IS |
| | NOT GIVEN THE ASSOCIATED PRESSURES ARE GIVEN. |
| | WINDOW AND DOOR PRESSURES ARE LISTED AS +30,4/ -33.5 |
| | BUT THE SQUARE FOOTAGE OF THE OPENING IS NOT GIVEN. IT |
| | IS ASSUMED THESE PRESSURES ARE IN VASD. |
| | THE ROOF PRESSURES 1 & 2 APPEAR TO BE IN VASD, ZONE 3 |
| | PRESSURES ARE LOW. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 9.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 9.2. RISK CATEGORY. |
| | |
| | 9.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | |
| | 9.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 9.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | |
| | 9.6 MEAN ROOF HEIGHT. |
| | |
| | 10) PLEASE PROVIDE THE SHOP DRAWINGS& CALCULATIONS FOR |
| | THE COLD-FORMED STEEL LIGHT-FRAME BUILDING. |
| | 10A) 2211.2 HEADER DESIGN. HEADERS, INCLUDING BOX AND |
| | BACK- TO-BACK HEADERS, AND DOUBLE AND SINGLE L-HEADERS |
| | SHALL BE DESIGNED IN ACCORDANCE WITH AISI S212 OR AISI |
| | S100. |
| | |
| | 10B) 2211.3 TRUSS DESIGN. COLD-FORMED STEEL TRUSSES |
| | SHALL BE DESIGNED IN ACCORDANCE WITH AISI S214, |
| | SECTIONS 2211.3.1 THROUGH 2211.3.4 AND ACCEPTED |
| | ENGINEERING PRACTICE. |
| | |
| | 10C) 2211.4 WALL STUD DESIGN. WALL STUDS SHALL BE |
| | DESIGNED IN ACCORDANCE WITH EITHER AISI S211 OR AISI |
| | S100. |
| | |
| | 10D) 2211.5 FLOOR AND ROOF SYSTEM DESIGN. FRAMING FOR |
| | FLOOR AND ROOF SYSTEMS IN BUILDINGS SHALL BE DESIGNED |
| | IN ACCORDANCE WITH EITHER AISI S210 OR AISI S100. |
| | 2007AISI S100 D6.2.1(A) STRENGTH (RESISTANCE) OF |
| | STANDING SEAM ROOFING PANEL SYSTEM. PROVIDE |
| | CALCULATIONS FOR THE ROOFING AND WALL PANEL SYSTEMS. |
| | IDENTIFY WHICH SYSTEM IS BEING INSTALLED AND GAUGE OF |
| | THE MATERIAL. |
| | |
| | |
| | 10E) 2211.6 LATERAL DESIGN. LIGHT-FRAME SHEAR WALLS, |
| | DIAGONAL STRAP BRACING THAT IS PART OF A STRUCTURAL |
| | WALL AND DIAPHRAGMS USED TO RESIST WIND, SEISMIC AND |
| | OTHER IN-PLANE LATERAL LOADS SHALL BE DESIGNED IN |
| | ACCORDANCE WITH AISI S213. |
| | |
| | 11) SHEET 4 OF 13 SHOWS THE ACCESSIBLE RESTROOM WITH |
| | THE BACK WALL MEASUREMENT OF 6FT. PLEASE SHOW |
| | COMPLIANCE WITH 2014 FBC-ACCESS. CODE 604.3.1. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | |
| | 12) PLEASE SHOW ELEVATION VIEWS OF THE RESTROOM FOR THE |
| | OTHER ACCESSIBLE ELEMENTS IN THE RESTROOM. |
| | 2014 ACCESS. CODE SEE CHAPTER 6. 604.5 GRAB BARS, |
| | BACKING & 606 LAVATORIES. |
| | |
| | 13) THE SITE PLAN WILL NEED TO SHOW ACCESSIBLE PARKING |
| | SPACES THAT WILL MEET THE W. P. B. ACCESSIBLE STALL |
| | PARKING SPACE. ADVISORY 502.3.3 MARKING. THE METHOD AND |
| | COLOR OF MARKING ARE NOT SPECIFIED BY THESE |
| | REQUIREMENTS BUT MAY BE ADDRESSED BY STATE OR LOCAL |
| | LAWS OR REGULATIONS. BECAUSE THESE REQUIREMENTS PERMIT |
| | THE VAN ACCESS AISLE TO BE AS WIDE AS A PARKING SPACE, |
| | IT IS IMPORTANT THAT THE AISLE BE CLEARLY MARKED. |
| | |
| | 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |