| Notes |
| Date |
Text |
| 2016-04-27 11:07:16 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | NEC 240.21 C(1) , NEC 240.21 C(4) TRANSFORMER SECONDARY | | | CONDUCTORS MUST TERMINATE TO A OVERCURRENT PROTECTION | | | DEVICE. REFERENCE TABLE NEC 450.3 (B) | | | NEC 240.21 B(5) FEEDER TAP CONDUCTORS MUST BE PROTECTED | | | BY A OVERCURRENT PROTECTION. REFERENCE NEC 408.36 | | | PANELBOARD PROTECTION. | | | RISER DIAGRAM SHOWS EQUIPMENT "T1" , "T2" , "TL" AS MLO | | | AND PANEL SCHEDULE REFLECTS MCB ? CLARIFY AND RE-ADJUST | | | ACCORDINGLY. | | | |
|