| Plan Review Notes For Permit 16040952 |
| Permit Number |
16040952 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-29 03:38:31 | 1) INDICATE THE TYPE OF "FLEX" PIPE SHOWN ON THE GAS | | | DRAWING. IS IT CSST? IF SO, SUBMIT THE CORRESPONDING | | | EHD NUMBER FOR THE SIZE OF THE TUBING. COMPLY WITH | | | TABLE 402.4 (15) OF THE 2014 FGC. NOTE: THERE IS NO | | | SIZING TABLE FOR "FLEX" PIPE IN THE GAS CODE. | | | 2) IF THE "FLEX" TUBING IS NOT CSST, SUBMIT | | | MANUFACTURER'S SPECIFICATIONS (2 COPIES) FOR THIS | | | MATERIAL. THE MATERIAL SHALL BE RATED FOR USE WITH | | | NATURAL GAS. 2014 FGC SEC.403.1, 403.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|