| Plan Review Notes For Permit 16040931 |
| Permit Number |
16040931 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-18 18:44:14 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | NEC 210.52 (A) RECEPTACLES SHALL BE INSTALLED IN THE | | | SUNROOM PROVIDE FLOOR PLAN SHOWING THE OUTLETS. | | | NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE | | | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY | | | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 | | | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE | | | DISTANCE FROM THE EDGE OF THE WALL. | | | NEC 210.52 (A)(2) WALL SPACE. ANY WALL SPACE 2 FT. OR | | | MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. | | | NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. | | | SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS 314 | | | & 315. |
|