| 2016-12-30 14:07:57 | RESIDENTIAL (R3) FRONT REVISION, THIRD MECHANICAL |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | ENGINEER OF RECORD MAY BE CHARGED A FOUR TIMES THE PLAN |
| | REVIEW FEE IF PLANS ARE DENIED 3 TIMES OR MORE. SEE |
| | FLORIDA STATUTE 553.80(2)(B). |
| | |
| | ORIGINAL COMMENT: |
| | 1- PLANS NEED TO PROVIDE COMPLIANCE WITH THE BALANCED |
| | RETURN AIR OF ALL ROOMS AS REQUIRED BY SEC. M1602.4 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | RESPONSE: |
| | SIZE OF TRANSFER DUCTS SPECIFIED ON SHEET A3 DON'T |
| | COMPLY WITH SEC. M1602.4 FBC-RESIDENTIAL. BEDROOM #4 |
| | NEEDS AT LEAST 9" DUCT AND BEDROOMS #2 AND #3 NEED AT |
| | LEAST 10" DUCT. REVISE AS REQUIRED. NOTE: ALSO, REVISED |
| | BEDROOM # TO MATCH FLOOR PLAN ON SHEET A1. THERE ARE |
| | ONLY 3 BEDROOMS IN THIS HOUSE NOT 4. REVISE AS |
| | REQUIRED. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 2- REVISE THE EQUIPMENT SIZING CALCULATIONS. PLANS WERE |
| | REVISED TO DISCARD THE ADDITION. EQUIPMENT SIZING |
| | CALCULATIONS WERE NOT REVISED. NOTE: CALCULATIONS |
| | SUBMITTED ARE DONE USING OLD SOFTWARE. PROVIDE REVISED |
| | EQUIPMENT SIZING CALCULATIONS USING CURRENT VERSION OF |
| | ENERGY SOFTWARE. (OR USE ANY OTHER APPROVED SOFTWARE). |
| | PLEASE MAKE SURE CALCULATIONS ARE DONE BASED ON THE |
| | ACTUAL ORIENTATION OF THE BUILDING TO AVOID |
| | CONFLICTS/DELAYS. SEC. R403.6.1 FBC-ENERGY |
| | CONSERVATION, 5TH EDITION (2014). |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. REVISED CALCULATIONS |
| | WERE NOT RE-SUBMITTED. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 3- EQUIPMENT LISTED ON THE A/C PLAN SUBMITTED DOESN'T |
| | MATCH EQUIPMENT LISTED IN THE EQUIPMENT SIZING |
| | CALCULATIONS. REVISE AS REQUIRED. SEC. R403.6.1 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | RESPONSE: |
| | THIS CAN NOT BE REVIEWED AT THIS TIME BECAUSE REVISED |
| | EQUIPMENT SIZING CALCULATIONS WERE NOT SUBMITTED. |
| | |
| | |
| | NOTE: PROVIDE AHRI CERTIFICATE FOR FINAL INSPECTION. |
| | |
| | |
| | ****ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD |
| | SHEET. DON'T STAPLE OLD DRAWINGS TO NEW SET. SUBMITT |
| | OLD DRAWINGS FOR REFERENCE. |
| | |