Plan Review Notes
Plan Review Notes For Permit 16040915
Permit Number 16040915
Review Stop B
Sequence Number 3
Notes
Date Text
2016-12-27 17:01:56 
  
 NOTE: REVISION FEES ARE NO PAID. NEED TO PAY REVISION
 FEES FOR FURTHER REVIEW.
  
  
  
 RESIDENTIAL (R3) FRONT BUILDING REVISION, THIRD
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED A FOUR TIMES THE PLAN
 REVIEW FEE IF PLANS ARE DENIED 3 TIMES OR MORE. SEE
 FLORIDA STATUTE 553.80(2)(B).
  
 1- STEEL SHOP DRAWINGS SUBMITTED FROM JAMES F. GIAGI,
 P.E. DON'T MATCH STRUCTURAL DRAWINGS SHOWN BY THE
 ENGINEER OF RECORD DONALD M. DIXON. STRUCTURAL ENGINEER
 OF RECORD SHOWS TWO C10X20 STEEL CHANNELS RESTING ON
 EXISTING DOUBLE WOOD PLATES. STEEL SHOP DRAWINGS SHOW
 ONE W10X60 RESTING ON STEEL COLUMNS AND CORRESPONDING
 FOOTING. STEEL SHOP DRAWINGS SEEM TO BE MORE
 STRUCTURALLY SOUND. STRUCTURAL ENGINEER OF RECORD TO
 PROVIDE STRUCTURAL ANALYSIS OF ALL THE FRAMING MEMBERS
 SHOWING THE COMPLETE LOAD PATH OF THE PROPOSED STEEL
 BEAM. AND, PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR ALL FRAMING MEMBERS. SEC. R301.1 FBC-RESIDENTIAL-
 5TH EDITION, (2014).
  
 2- ENGINEER OF RECORD REVISED THE WIND DESIGN
 INFORMATION ON SHEET A1. CLARIFY WHY THE DESIGN WIND
 SPEED WAS REVISED FROM 175 MPH TO 140 MPH?. IS THIS THE
 ULTIMATE WIND LOAD OR THE NOMINAL WIND LOAD. IT IS NOT
 CLEAR. REVISE AS REQUIRED. SEC. R301.2.1.3
 FBC-RESIDENTIAL.
  
 3- NOTE #1 OF GENERAL SCOPE OF WORK ON SHEET A1 NOW
 SPECIFIES "DEMOLISH ENTIRE REMAINS OF THE FIRE DAMAGED
 ROOF AND INSTALL TOTALLY NEW ROOF". DRAWINGS SUBMITTED
 DON'T PROVIDE ANY DETAILS AND SPECIFICATIONS. COMPLETE
 FRAMING DETAILS AND SPECIFICATIONS FOR THE
 RE-CONSTRUCTION OF THE DAMAGED ROOF. SEC. R301.1
 FBC-RESIDENTIAL.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) EXTERIOR DOORS AS SHOWN ON PLANS. (NEED HISTORIC
 APPROVAL).
  
 B) ROOF TO BE INSTALLED. COORDINATE WITH ITEM #3 ABOVE.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE ROOF PRODUCT APPROVAL
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 ****ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD
 SHEET. DON'T STAPLE OLD DRAWINGS TO NEW SET. SUBMITT
 OLD DRAWINGS FOR REFERENCE.
  