| 2016-12-27 17:01:56 | |
| | |
| | NOTE: REVISION FEES ARE NO PAID. NEED TO PAY REVISION |
| | FEES FOR FURTHER REVIEW. |
| | |
| | |
| | |
| | RESIDENTIAL (R3) FRONT BUILDING REVISION, THIRD |
| | BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | NOTE: |
| | ENGINEER OF RECORD MAY BE CHARGED A FOUR TIMES THE PLAN |
| | REVIEW FEE IF PLANS ARE DENIED 3 TIMES OR MORE. SEE |
| | FLORIDA STATUTE 553.80(2)(B). |
| | |
| | 1- STEEL SHOP DRAWINGS SUBMITTED FROM JAMES F. GIAGI, |
| | P.E. DON'T MATCH STRUCTURAL DRAWINGS SHOWN BY THE |
| | ENGINEER OF RECORD DONALD M. DIXON. STRUCTURAL ENGINEER |
| | OF RECORD SHOWS TWO C10X20 STEEL CHANNELS RESTING ON |
| | EXISTING DOUBLE WOOD PLATES. STEEL SHOP DRAWINGS SHOW |
| | ONE W10X60 RESTING ON STEEL COLUMNS AND CORRESPONDING |
| | FOOTING. STEEL SHOP DRAWINGS SEEM TO BE MORE |
| | STRUCTURALLY SOUND. STRUCTURAL ENGINEER OF RECORD TO |
| | PROVIDE STRUCTURAL ANALYSIS OF ALL THE FRAMING MEMBERS |
| | SHOWING THE COMPLETE LOAD PATH OF THE PROPOSED STEEL |
| | BEAM. AND, PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| | FOR ALL FRAMING MEMBERS. SEC. R301.1 FBC-RESIDENTIAL- |
| | 5TH EDITION, (2014). |
| | |
| | 2- ENGINEER OF RECORD REVISED THE WIND DESIGN |
| | INFORMATION ON SHEET A1. CLARIFY WHY THE DESIGN WIND |
| | SPEED WAS REVISED FROM 175 MPH TO 140 MPH?. IS THIS THE |
| | ULTIMATE WIND LOAD OR THE NOMINAL WIND LOAD. IT IS NOT |
| | CLEAR. REVISE AS REQUIRED. SEC. R301.2.1.3 |
| | FBC-RESIDENTIAL. |
| | |
| | 3- NOTE #1 OF GENERAL SCOPE OF WORK ON SHEET A1 NOW |
| | SPECIFIES "DEMOLISH ENTIRE REMAINS OF THE FIRE DAMAGED |
| | ROOF AND INSTALL TOTALLY NEW ROOF". DRAWINGS SUBMITTED |
| | DON'T PROVIDE ANY DETAILS AND SPECIFICATIONS. COMPLETE |
| | FRAMING DETAILS AND SPECIFICATIONS FOR THE |
| | RE-CONSTRUCTION OF THE DAMAGED ROOF. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) EXTERIOR DOORS AS SHOWN ON PLANS. (NEED HISTORIC |
| | APPROVAL). |
| | |
| | B) ROOF TO BE INSTALLED. COORDINATE WITH ITEM #3 ABOVE. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE ROOF PRODUCT APPROVAL |
| | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | |
| | ****ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD |
| | SHEET. DON'T STAPLE OLD DRAWINGS TO NEW SET. SUBMITT |
| | OLD DRAWINGS FOR REFERENCE. |
| | |